background image

3

1.2    

MAXX

SST

3000 Safety Features

Built-in Safety Features include: 
• Automatic overload (over-temperature) shutdown and reset (activated if AC output

exceeds 6000 watts for more than 3 seconds)

• Automatic AC short-circuit shutdown and reset
• Automatic low voltage audible alarm and reset (sounds at 10.6 volts input)
• Automatic low-voltage shutdown and reset (activates at 10.0 volts DC)
• Automatic high-input voltage shutdown and reset (activates at above 

15 volts DC)

WARNING

The 

MAXX

SST

3000

output should be treated with the same caution as any

110 volt AC circuit. It is very important that anyone who is installing or using the
inverter read and follow all instructions provided in this manual to ensure optimum
safety and performance.

When you use the high output direct wiring feature with the required user-supplied
dual ganged 25 amp circuit breaker, the 

MAXX

SST

3000

can be installed with

an automatic transfer switch or manual transfer switch. Then, when utility power (or
generator-supplied power) is lost, the inverter will supply the necessary power to
the appliance circuits.

The 

MAXX

SST

3000

is ideal for powering:

• TV/VCR combinations
• Refrigerator/freezers
• Lights
• Radio receivers/transceivers
• Heavy duty power tools & chargers
• Stereo systems
• Microwave ovens
• Household appliances
• Computers and peripheral equipment
• Dry and/or wet/dry vacuums
• Sump pumps, motors, and other electric-powered equipment
• Air compressors
• Many more appliances, products and devices

The 

MAXX

SST

3000

uses a 12 VDC power source like those found in 12 VDC

motor vehicles or boats or it can be operated using multiple battery configurations
with commercial battery chargers or solar battery chargers.   For most heavy-duty
applications, a multiple battery configuration and the use of deep-cycle batteries
is a requirement.

24

Figure 9. Connections to the High Output Terminal Block.

30

All wire cable used to make a connection to the High Output Terminal Block should
be insulated and rated at #10 AWG to carry 30 amps. These common cables are
normally color coded Black for the “hot” wire; White for the “neutral” wire and
bare Copper or Green for the ground wire. If this wiring is to be permanently used
in fixed locations, ordinary single conductor wire cable is acceptable. If the cable
will be used in a mobile environment, multi-stranded wire should be used.
Multi-stranded wire can withstand constant cable flexing, while single conductor
(one strand wire) cable cannot. When making connections to the High Output
Terminal Block, follow the wiring configurations shown in FIGURE 9 That is: black
to black, white to white and bare or green to ground. Note that the designation of
the terminals on the inverter are labeled L, N, and ground symbol. “L” stands for
“load”, the “hot” terminal. "N" stands for "Neutral". The breaker should be mount-
ed in a metal box for that breaker type. When you purchase a breaker and box,
ensure that they are intended for use together. Locate the 110 VAC breaker box
near the inverter terminals to ensure access to the breaker if it trips.

If the High Output Terminal block wiring is used with existing wiring, ensure that the
AC from the inverter is protected with a dual ganged 30 amp circuit breaker and
is isolated from other sources of AC by using a transfer switch that simultaneously
switches Neutral and Hot output. Refer to 

FIGURE 4

as a guide to wiring to a

transfer switch. 

(Rear Panel of Inverter)

Содержание MAXX SST 3000 VEC051

Страница 1: ...d unit of the same or comparable design The repaired or replaced unit will then be warranted under the terms of the remainder of the warranty period The customer is responsible for the shipping charge...

Страница 2: ...THIS POWER INVERTER WARNINGS TO REDUCE THE RISK OF FIRE ELECTRIC SHOCK EXPLOSION OR INJURY Do not connect to AC distribution wiring Remove appliance plug from outlet strip or turn off inverter before...

Страница 3: ...12 VDC battery supply Switch OFF the inverter clean input terminals reconnect input terminals and cable ends reconnect cables Input power source below 10 VDC Recharge or replace power source batterie...

Страница 4: ...inverter shutdown is removed Previously manual reset was required This power inverter also incorporates a new cooling technology that directly benefits our customers The new design more efficiently co...

Страница 5: ...ill automatically shut down until the condition improves FIGURE 2 shows the back panel DC connectors and fan locations Note that the fan only operates when the inverter temperature rises It shuts off...

Страница 6: ...tery configurations with commercial battery chargers or solar battery chargers For most heavy duty applications a multiple battery configuration and the use of deep cycle batteries is a requirement 24...

Страница 7: ...NG NO USER SERVICEABLE COMPONENTS INSIDE OPENING UNIT WILL VOID WARRANTY 23 16 Connect an insulated wire at least 12 AWG between the grounding screw on the inverter s enclosure and a solid electrical...

Страница 8: ...surface that you have selected 2 Mount the fuse holder to its mounting surface using appropriate hardware Ensure that the mounting hardware does not touch any of the fuse holder contacts or fuse conta...

Страница 9: ...battery power you will need Ring terminals to connect two 0000 4 0 cables to the battery bank A single length of not more than ten feet of 0000 4 0 multi stranded flexible insulated cable A 500 amper...

Страница 10: ...e 1 Identify the positive and negative terminals on the 12 volt DC battery and identify the positive and negative terminals on the inverter 2 Remove the plastic terminal cover 3 Using the set of heavy...

Страница 11: ...e ability to operate reactive loads such as those found in inductive motors 19 CAUTIONS This device supplies 110 VAC electrical power directly to the appliances through two standard North American 3 c...

Страница 12: ...llow simultaneous operation of all the AC appliances to be powered with delay characteristics that allow for the momentary high start up current requirements of inductive loads Use the recommended fus...

Страница 13: ...t peak limit the inverter will automatically shut down Once the excessive load is removed the inverter can be restarted and resume normal operation Note If overload shutdown occurs turn OFF the unit a...

Страница 14: ...3 The inverter is in thermal shutdown NOTE It is normal for the alarm to sound when the MAXXSST 3000 is being connected to or disconnected from a 12 VDC power source This does NOT indicate a problem...

Страница 15: ...e indicator will be in the upper red zone Although the inverter has built in protection against overvoltage it may still be damaged if the input voltage exceeds 15 2 volts NOTE Exceeding the recommend...

Страница 16: ...time of 5 minutes but it maintains the temperature of the pot at about 100 watts Typical use of a microwave is only for a few minutes sometimes at low power Some typical exceptions to brief operating...

Отзывы: