OPA2-MOD(-H)

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

Programmable operation terminal for MODBUS 

OPA2-MOD 

 

Features 

 

LCD display with backlight four keys 

 

Internal temperature sensor 

 

With –H model, internal humidity sensor 

 

1 external temperature input 

 

2 digital inputs, which can be configured for window/door contacts 
or motion detectors.  

 

Up to 5 zones may be handled by one operation terminal 

 

Detailed configuration possible 

 

RS485 2-wire MODBUS standard in accordance to EIA/TIA 485 

 

Slave type of communication 

 

Galvanic isolated bus connection 

 

Flush mounted on standard EU/UK/CH installation box 

Application 

The operation terminal controls typically a single room control unit. The device measures room temperature and humidity 

(for –H type) through integrated sensors. Two additional digital inputs may be configured for window contact, key 

switches or motion detectors. The operation mode may then be controlled based on these inputs. An external temperature 

may be measured through the additional temperature input. This may be useful for underfloor heating, sensor averaging 

for large rooms, outdoor temperatures etc.  

The operation terminal communicates through a galvanically isolated RS485 interface via the MODBUS protocol in slave 

mode.  

Ordering  

Model 

Item#  Display 

RT 

DI 

rH 

Description 

OPA2-MOD 

40-50 0014 

yes 

Modbus communication module with one internal 
temperature sensor and one external temperature 
input plus two binary inputs.  

OPA2-MOD-H 

40-50 0053 

yes 

As above with internal humidity sensor 3% 
accuracy.  

Supported Modbus commands: 

-

 

03 (0x03): Read multiple registers 

-

 

06 (0x06): Write single register 

-

 

16 (0x10): Write multiple registers 

 

Commands 03 and 16 can handle up to 32 registers. The Modbus slave transmits the values as signed 16 bit integers with 

one digit below the decimal point. This results in the following range: -9999.9 to 9999.9 

 

In an event of an out-of-range command addressing or an unsupported command, the Modbus slave responds with an 
exception message according to the Modbus specification. 

Dimensions [mm](in) 

 

 

88 (3.5) 

32 

(1.2) 

21  

(0.8) 

8

8

 (

3

.5

5

8

 

(2

.3

Содержание 40-50 0014

Страница 1: ...lled based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatures etc The operation terminal communicates through a galvanically isolated RS485 interface via the MODBUS protocol in slave mode Ordering Model Item Display RT DI rH Description OPA2 MOD 40 50 0014 y...

Страница 2: ...l be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft Environment Operation Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing class 2M2 Transport Storage Climatic Conditions Tempe...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Verify that the mounting screw heads do not stand ...

Страница 4: ...successfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The selected sensor is not enabled No The change of setpoint or operation mode is disabled or the remote disable function is active Left POWER Toggle ON OFF mode Parameter setting ENTER to select menu o...

Страница 5: ... selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode change occupied unoccupied enabled 0 disabled 1 enabled 0 1 1 CP 09 24h 12h 0 24h 1 12h AM PM 0 1 0 CP 10 This setting is not used 0 1 0 CP 11 Celsius Fahrenheit 0 Celsius 1 Fahrenheit 0 1 0 CP 12 Ti...

Страница 6: ...PM 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If enabled shows a specific screen if no key is pressed for the time defined in 1016 1018 Byte R W Maximum number of FAN speeds 1 3 This setting applies if number of groups is set to one group with fan sp...

Страница 7: ...number of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W Show cooling symbol 0 2009 bit R W Show comfort operation mode symbol 0 2010 bit R W Show standby operation mode symbol 0 2011 16 bit R W Show arrow 0 10 LSb Arrow 1 on the left 0 2012 8bit ASCII R W...

Страница 8: ... value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 or 7005 depending on operation mode 8 value zone 4 8001 9 setpoint zone 4 8004 or 8005 depending on operation mode 10 value zone 5 9001 11 setpoint zone 5 9004 or 9005 depending on operation mode 12 C...

Страница 9: ...12 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2 value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004...

Страница 10: ...ext string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W Comfort setpoint 20 0 5005 16 bit signed R W Standby setpoint 20 0 5006 16 bit signed R W Setpoint step 0 1 0 5 1 0 2 0 5 0 5007 16 bit signed R W Low setpoint limit 16 0 5008 16 bit signed R W High ...

Страница 11: ...3 byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 10307 byte R W Digital input 1 closed character 02 O 10308 byte R W Digital input 1 closed character 03 N 10309 byte R W Digital input 1 closed character 04 10400 bit R W Digital input 2 function assi...

Страница 12: ...byte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4 2 11012 byte R W FAN string 4 character 1 F 11013 byte R W FAN string 4 character 2 A 11014 byte R W FAN string 4 character 3 N 11015 byte R W FAN string 4 character 4 3 Reduced ASCII table for disp...

Отзывы: