OPA2-MOD(-H) 

Configuration

 

 

Doc: 70-00-0290, V1.0 R0, Date: 20160208 

© Vector Controls GmbH, Switzerland 

Page 8 

Subject to alteration 

Display in OFF mode 

Address 

Type 

R/W 

Contents 

3000 

Selection 

R/W 

Contents of large digits:  

0 = empty 

1 = text string OFF 

2 = value zone 1 (5001) 

3 = setpoint zone 1(5004 or 5005 depending on operation mode) 

4 = value zone 2 (6001) 

5 = setpoint zone 2(6004 or 6005 depending on operation mode) 

6 = value zone 3 (7001) 

7 = setpoint zone 3(7004 or 7005 depending on operation mode) 

8 = value zone 4 (8001) 

9 = setpoint zone 4(8004 or 8005 depending on operation mode) 

10 = value zone 5 (9001) 

11 = setpoint zone 5(9004 or 9005 depending on operation mode) 

12 = Clock 

13 = Alarm text 
14 = Internal temperature 

15 = External temperature 

16 = Relative humidity 

17 = Digital input 1 

18 = Digital input 2 

3001 

Selection 

R/W 

Contents of small digits:  

0 = empty 

1 = text string OFF

 

2 = value zone 1 (5001) 

3 = setpoint zone 1(5004 or 5005 depending on operation mode) 

4 = value zone 2 (6001) 

5 = setpoint zone 2(6004 or 6005 depending on operation mode) 

6 = value zone 3 (7001) 

7 = setpoint zone 3(7004 or 7005 depending on operation mode) 

8 = value zone 4 (8001) 

9 = setpoint zone 4(8004 or 8005 depending on operation mode) 

10 = value zone 5 (9001) 

11 = setpoint zone 5(9004 or 9005 depending on operation mode) 

12 = Clock 

13 = Alarm text 
14 = Internal temperature 

15 = External temperature 

16 = Relative humidity 

17 = Digital input 1 

18 = Digital input 2 

3002 

Selection 

R/W 

Contents of vertical bar:  

0 = empty

 

1 = bar of zone 1 

2 = bar of zone 2 

3 = bar of zone 3 

4 = bar of zone 4 

5 = bar of zone 5 

3003 

Selection 

R/W 

Show state of following symbols in OFF mode:  

bit select for symbols: 

Default 

bit 0 = Fan symbol 

0

 

bit 1 = Alarm symbol 

1

 

bit 2 = Heating/cooling 

1

 

bit 3 = Comfort/Standby 

0

 

bit 4 = Arrows 

1

 

3004 

8bit (ASCII) 

R/W 

Text string OFF letter 1:  

 

3005 

8bit (ASCII) 

R/W 

Text string OFF letter 2:  

3006 

8bit (ASCII) 

R/W 

Text string OFF letter 3:  

3007 

8bit (ASCII) 

R/W 

Text string OFF letter 4:  

 

 

Содержание 40-50 0014

Страница 1: ...lled based on these inputs An external temperature may be measured through the additional temperature input This may be useful for underfloor heating sensor averaging for large rooms outdoor temperatures etc The operation terminal communicates through a galvanically isolated RS485 interface via the MODBUS protocol in slave mode Ordering Model Item Display RT DI rH Description OPA2 MOD 40 50 0014 y...

Страница 2: ...l be connected between the terminals and of the furthermost node of the network Network topology Daisy chain according EIA TIA 485 specifications Recommended maximum length per chain 1200 m 4000 ft Environment Operation Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 r H non condensing class 2M2 Transport Storage Climatic Conditions Tempe...

Страница 3: ...above air discharge grills and diffusers Location of mounting is less critical if external temperature sensors are used Installation 1 Connect the wires to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is facing to the ground Verify that the mounting screw heads do not stand ...

Страница 4: ...successfully for the time period defined with CP18 1022 Verify wiring or operation of Modbus master device To disable this error set CP18 1022 to 0 Err2 The selected sensor is damaged or missing NA The selected sensor is not enabled No The change of setpoint or operation mode is disabled or the remote disable function is active Left POWER Toggle ON OFF mode Parameter setting ENTER to select menu o...

Страница 5: ... selection on right key 1 one zone 5 five zones 0 5 1 CP 06 Setpoint change enable 0 disabled 1 enabled 0 1 1 CP 07 Operation mode change ON OFF enabled 0 disabled 1 enabled 0 1 1 CP 08 Operation mode change occupied unoccupied enabled 0 disabled 1 enabled 0 1 1 CP 09 24h 12h 0 24h 1 12h AM PM 0 1 0 CP 10 This setting is not used 0 1 0 CP 11 Celsius Fahrenheit 0 Celsius 1 Fahrenheit 0 1 0 CP 12 Ti...

Страница 6: ...PM 1014 Bit R W AM PM flag 0 AM 1 PM 1015 Bit R W Celsius Fahrenheit 0 Celsius 1 Fahrenheit 1016 Byte R W Timeout in seconds to idle mode 0 255 seconds 1017 Bit R W Idle mode 0 disabled 1 enabled If enabled shows a specific screen if no key is pressed for the time defined in 1016 1018 Byte R W Maximum number of FAN speeds 1 3 This setting applies if number of groups is set to one group with fan sp...

Страница 7: ...number of fan speeds 1 3 2003 8bit R W Actual fan speed 2004 bit R W Show fan symbol 0 2005 bit R W Show alarm symbol 0 2006 bit R W Show alarm string 0 2007 bit R W Show heating symbol 0 2008 bit R W Show cooling symbol 0 2009 bit R W Show comfort operation mode symbol 0 2010 bit R W Show standby operation mode symbol 0 2011 16 bit R W Show arrow 0 10 LSb Arrow 1 on the left 0 2012 8bit ASCII R W...

Страница 8: ... value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004 or 7005 depending on operation mode 8 value zone 4 8001 9 setpoint zone 4 8004 or 8005 depending on operation mode 10 value zone 5 9001 11 setpoint zone 5 9004 or 9005 depending on operation mode 12 C...

Страница 9: ...12 Clock 13 Alarm text 14 Internal temperature 15 External temperature 16 Relative humidity 17 Digital input 1 18 Digital input 2 4001 Selection R W Contents of small digits 0 empty 1 text string OFF 2 value zone 1 5001 3 setpoint zone 1 5004 or 5005 depending on operation mode 4 value zone 2 6001 5 setpoint zone 2 6004 or 6005 depending on operation mode 6 value zone 3 7001 7 setpoint zone 3 7004...

Страница 10: ...ext string group 1 2 value 3 setpoint Comfort standby depending on operation mode 4 Alarm text 5 internal NTC 6 external NTC 7 humidity value 8 digital input 1 9 digital input 2 5004 16 bit signed R W Comfort setpoint 20 0 5005 16 bit signed R W Standby setpoint 20 0 5006 16 bit signed R W Setpoint step 0 1 0 5 1 0 2 0 5 0 5007 16 bit signed R W Low setpoint limit 16 0 5008 16 bit signed R W High ...

Страница 11: ...3 byte R W Digital input 1 open character 02 O 10304 byte R W Digital input 1 open character 03 F 10305 byte R W Digital input 1 open character 04 F 10306 byte R W Digital input 1 closed character 01 10307 byte R W Digital input 1 closed character 02 O 10308 byte R W Digital input 1 closed character 03 N 10309 byte R W Digital input 1 closed character 04 10400 bit R W Digital input 2 function assi...

Страница 12: ...byte R W FAN string 2 character 4 1 11008 byte R W FAN string 3 character 1 F 11009 byte R W FAN string 3 character 2 A 11010 byte R W FAN string 3 character 3 N 11011 byte R W FAN string 3 character 4 2 11012 byte R W FAN string 4 character 1 F 11013 byte R W FAN string 4 character 2 A 11014 byte R W FAN string 4 character 3 N 11015 byte R W FAN string 4 character 4 3 Reduced ASCII table for disp...

Отзывы: