background image

 

TLC3-BCR-U Thermostat 

U

SER 

C

ONFIGURATION

 

 

Doc: 70-00-0294, V3.1, Date: 20140508 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

User and display parameters (password 009) 

 

Parameter  Description 

Range 

Default 

UP 00 

Enable change of operation modes,  

ON, OFF 

ON (Enabled) 

UP 01 

Enable change of set points 

ON, OFF 

ON (Enabled) 

UP 02 

Parameter not used 

ON, OFF 

ON 

UP 03 

Enable manual Heat/Cool change 

ON, OFF 

W00 = ON 

W01 = OFF 

UP 04 

Enable Access to time programs 

ON, OFF 

ON (Enabled) 

UP 05 

State after power failure: 0 = OFF, 1 = ON, 2 = Last State 

0, 1, 2 

UP 06 

Enable Economy (unoccupied) Mode.  
Shift the setpoint to a lower temperature in winter or higher 

temperature in summer in order to save energy. May be activated 

through the POWER button, or with the external input (typically for 

key card switches in hotel rooms or motion detectors for meeting 
rooms.)  

ON, OFF 

ON 

(Economy ) 

UP 07 

Celsius or Fahrenheit, OFF for Celsius, ON for Fahrenheit 

ON, OFF 

OFF (Celsius) 

UP 08 

Calibrate internal temperature sensor  
–10° to +10° in 0.1° steps. (Sensor is factory calibrated, use this 

feature for field adjustment only as required.) 

-10…10 

UP 09 

Enable Frost Protection.  
Switches to heating mode and activates the output when the control 

temperature drops below 5°C or 41°F. The controller returns to 

normal operation when the temperature increases above 10°C or 

50°F. 

ON, OFF 

W00 = ON 

W01 = OFF 

UP 10 

Select contents of Large LCD display in standard mode: 

0…6 

 

02  

Temperature 

00 = OFF 

01 = Setpoint 

02 = Temperature Sensor 

03 = Output Mode 

04 = Clock 

05 = Alternative Sensor 
06 = Changeover Sensor (X2) 

UP 11 

Select contents of small LCD display in standard mode 

0…6 

Standard:  

01 Setpoint 

Deluxe: 

04 Clock 

00 = OFF 

01 = Setpoint 

02 = Temperature Sensor 

03 = Output Mode 

04 = Clock 

05 = Alternative Sensor 
06 = Changeover Sensor (X2) 

UP 12 

Clock display type: Only available for deluxe version 

OFF = Show 24hour clock 

ON   = Show 12hour clock (AM, PM) 

ON, OFF 

OFF (24h) 

UP 13 

Reset timer for override mode: Only available for deluxe version 

= Reset of override mode is not active.  

1…255   = delay in minutes to switch off device if ON/Economy mode 

is activated while the unit is scheduled to be in OFF mode 

0…255 

60 (Min) 

 

Содержание 40-10 0160

Страница 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Страница 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Страница 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Страница 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Страница 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Страница 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Страница 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Страница 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Страница 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Страница 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...

Отзывы: