TLC3-BCR-U Thermostat 

O

PERATION

 

 

Doc: 70-00-0294, V3.1, Date: 20140508 

© Vector Controls GmbH, Switzerland 

Page 3 

Subject to alteration 

Connection  

 

Terminal Description  

 

Power supply:  

0V Neutral 

Power supply:  

230VAC 

Y1 

Binary output 230V AC:  

  

 

Heat for binary or PWM actuators if in 4-pipe or single stage mode 

 

 

Open for 3-point actuators 

 

 

Stage 1 if in reversing valve mode 

 

 

Stage 1 if in 2-stage mode 

 

Y2 

Binary output 230V AC:  

 

 

 

Cool for binary or PWM actuators if in 4-pipe mode or single stage mode 

 

 

Close for 3-point actuators 

 

 

Reversing valve if activated 

 

 

Stage 2 if 2-stage mode 

 

X1

  External input: 

NTC 10kΩ @ 25°C (77°F) or open contact to SGND 

 

 

Automatic detection for control input  

 

 

or according to setup 

 

X2

  External input: 

NTC 10kΩ @ 25°C (77°F) or open contact to SGND 

 

 

Changeover or remote control input 

 

Mounting location 

 

Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average 

temperature. 

 

Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.  

 

Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.  

 

Location of mounting is less critical if external temperature sensors are used. 

 

Ensure adequate air circulation to dissipate heat generated during operation. 

 

Observe local regulations. 

 

Do not mount in wet or condensation prone environments. 

Installation 

1.

 

Connect the wires to be connected to the terminals of the power case according to wiring diagram 

2.

 

Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is 

facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2”) off the 

surface of the mounting plate.  

3.

 

Ensure that the jumpers are set correctly.  

4.

 

Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.  

5.

 

Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle 

way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is 

normal. Do not use excessive force!  

6.

 

With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to the 

mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the screw too 

much. 

Warning:  
Live Electrical Components! 

During installation, testing, servicing and 
troubleshooting of Vector Controls 
products, it may be necessary to work with 
live electrical components. Have a qualified 

licensed electrician or other individual who 
has been properly trained in handling live 
electrical components perform these tasks. 
Failure to follow all electrical safety 
precautions when exposed to live electrical 
components could result in death or 
serious injury.

 

X

T INT 

0V 

230V AC 

 

TLC3-BCR-U 

X1 

X

T EXT

  

IN 

 

Y1 

Heat 

Open 

Y2 

Cool 

Close 

X1 

X

T EXT

  

IN 

 

X2 

X

T CO

  

IN 

 

X2 

X

T CO

  

IN 

 

Содержание 40-10 0160

Страница 1: ...n General temperature control General TLC3 BCR U 1 independent temperature control loop with 1 heating and 1 cooling sequence 1 internal temperature sensor 1 external temperature input 1 auxiliary inp...

Страница 2: ...ng Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing class 2M2 Standards...

Страница 3: ...e wires to be connected to the terminals of the power case according to wiring diagram 2 Install the mounting plate to the flush mounting box Make sure that the nipple with the front holding screw is...

Страница 4: ...ints are memorized and do not need to be re entered Upon return of power Set Parameter UP05 to keep the unit off switch on or operation mode before power failure Clock and time schedule settings retai...

Страница 5: ...to Pro 4 PRO 1 is shown 1 is blinking UP DOWN to change OPTION to select SEL PRO Pro 1 to Pro 4 OFF ON Step 2 Enable disable time schedule group Pro x is fixed now ON OFF blinks Press UP DOWN to set...

Страница 6: ...f inputs and type of outputs 241 How to change parameters 1 Press UP DOWN buttons simultaneously for three seconds The display will show firmware version and revision number Press the OPTION button to...

Страница 7: ...rnal temperature sensor 10 to 10 in 0 1 steps Sensor is factory calibrated use this feature for field adjustment only as required 10 10 0 UP 09 Enable Frost Protection Switches to heating mode and act...

Страница 8: ...t persist for the length of time set with this parameter before the controller switches Prevents activation of a sequence during a short term change in temperature in order to protect equipment with c...

Страница 9: ...alve or damper to the closed position The running time of the actuator may be preset We recommend to enter the maximum running time under maximum load in order to make sure that the valve can fully cl...

Страница 10: ...ting X2 input to GND returns control of the operation mode to the terminal This function may be used as window contact to prevent loss of energy CP17 3 Heat Cool changeover Switch heating and cooling...

Отзывы: