background image

Page 6

Airflow adjustment for Left-Hand Drainage

1.  For left hand drainage as shown on Page 5, ensure that the jumper switch JP4 (see diagram above) is in 

Position B.

Normal (trickle) speed  (l/h drainage)

2. Before making any adjustments, switch on the unit at trickle speed.  

WARNINg : 230 volt, live mains are 

present on the circuit board.

Move the speed adjust jumper switch JP5, to position A, as shown in the 

diagram. A green light will appear on the circuit board.--

3. With the boost switch OFF (bathroom light switch off), measure the airflow rate at the extract valve and 

compare this to the design value. If there is a difference, adjust the potentiometer MIN-MOT1, on the con-
trol  board and re-check the airflow rate. If the value is slightly higher than that required, final adjustment 
can be made at the air valve. 

4. Set the position of the potentiometer MIN-MOT2 to the same as MIN-MOT1.
5. Measure the airflow at the supply valve. This should be the same or slightly lower than the extract rate 

(

unless a different supply value has been specified).  If higher, reduce the airflow by adjusting MIN-MOT2.  

Final, minor adjustments can be made at the air valve. 

Boost speed (l/h drainage)

6. Switch on the boost (light switch ON).
7. Measure the airflow rate at the extract valve and compare this to the design value. If there is a difference, 

adjust the potentiometer MAX-MOT1.

8. Re-check the airflow rate and make further adjustments at MAX-MOT1 until correct.  

Do not re-adjust the

air valve.

9. Set the position of the potentiometer MAX-MOT2 to the same as MAX-MOT1.
10.  Measure the airflow at the supply valve. This should be the same or slightly lower than the extract rate.

*

If higher, reduce the airflow by adjusting MAX-MOT2 until correct. 

Do not re-adjust the air valve

.

*

unless a different supply value has been specified.

11.  Return the speed adjust jumper switch JP5, to position B (green light goes out)

Timer Overrun Adjustment

After the boost switch has been turned off, the fan will continue to run at boost speed for up to 20 minutes.
This overrun time is adjustable using the potentiometer marked TIMER. The time can be varied between 0 and
20 
minutes. After the set time, the fan returns to normal speed.

Delay-on Boost

When the boost switch is operated, the boost speed activation can be delayed by 2 minutes, if required. 
Using the jumper switch JP6, move the jumper position to either:-

A

-  2 minutes, or 

B

-  0.5 seconds

Finally, replace the control panel cover securely.

Controller Adjustment diagram

Содержание WHHR100DC-B Plus

Страница 1: ...WHHR100 90DC B Plus Whole House Heat Recovery Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructions...

Страница 2: ...nt avoiding the use of excessive energy and saving heat already generated The heat recovery unit will generally be installed in the loft of a house or the void above the ceiling in an apartment but ma...

Страница 3: ...le the unit should NOT be installed directly above a bedroom or living room The condensation drain must be fitted and if insulated use the equivalent of at least 25mm of insulating material with a the...

Страница 4: ...5mm of insulating material with a thermal conductivity of 0 04 W mK The pipe must drain into the normal household drainage system The drain must incorporate a wet or dry trap to prevent air penetratio...

Страница 5: ...esign value If incorrect adjust as follows Turn the electrical supply off Remove the cover of the electrical control panel Adjust the potentiometer marked min up or down as required See page 6 Turn on...

Страница 6: ...Page 6 Vectaire Ltd Lincoln Road Cressex Business Park High Wycombe Buckinghamshire HP12 3RH Tel 44 0 1494 522333 Fax 44 0 1494 522337 Email sales vectaire co uk WHHR100 90DC B Plus Oct 2014 E O E...

Страница 7: ...WHHR100 90DC B Plus Bypass models Whole House Heat Recovery Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructions...

Страница 8: ...lthy environment avoiding the use of excessive energy and saving heat already generated The heat recovery unit will generally be installed in the loft of a house or the void above the ceiling in an ap...

Страница 9: ...ssible the unit should NOT be installed directly above a bedroom or living room The condensation drain must be fitted and if insulated use the equivalent of at least 25mm of insulating material with a...

Страница 10: ...5mm of insulating material with a thermal conductivity of 0 04 W mK The pipe must drain into the normal household drainage system The drain must incorporate a wet or dry trap to prevent air penetratio...

Страница 11: ...am A green light will appear on the circuit board 3 With the boost switch OFF bathroom light switch off measure the airflow rate at the extract valve and compare this to the design value If there is a...

Страница 12: ...valve Boost speed l h drainage 6 Switch on the boost light switch ON 7 Measure the airflow rate at the extract valve and compare this to the design value If there is a difference adjust the potentiom...

Страница 13: ...ain access panel Remove the rubber inserts from the filter slots where fitted and slide out the filters from the internal mouldings Clean the filters carefully using a vacuum cleaner and refit Replace...

Отзывы: