2 - GENERAL DESCRIPTION OF THE VEGA MK II PANEL
Pag.
5
Temperature probes setting out parameters
Parameter C95
It is the internal probe offset. This parameter is used to change the temperature felt by
the internal probe. The value displayed in the parameter C95 is subtracted to the real
value read by the probe.
For example:
C95=3
Real temperature felt by the probe=25° C
Changed and displayed temperature=25-3=22° C
Parameter C96
It is the external probe offset.
This parameter is used to change the temperature felt by the external probe. The
value displayed is added (if positive) or subtracted (if negative) to the real temperatu-
re felt by the probe.
For example:
C96=3
Real temperature felt by the probe=25° C
Changed and displayed temperature=25+3=28° C
Real temperature felt by the probe=25° C
Changed and displayed temperature=25-3=22° C