AW 12s-62s, 12a-62a
15
Electrical connections for AW-s models
1. The work must be done by a qualified electrician.
2. The fan heater is constructed for 230 VAC.
3. The fan heater must be connected to the mains with a permanent cable. A multi-pole breaker with a
minimum of 3 mm between the poles must be used for the permanent connection.
4. Remove the lid to the connection box, as in photo 18.
5. Connections for the fan heater and the selection of fan speed are to be made according to the wiring
diagram inside the cover, see photo 19 or appendix E.
6. Use a hammer and a screwdriver to remove the required number of cable blanks (see photo 20).
Break off the blanks with pliers, as in photo 21.
7. The thermostat that controls the fan heater must be installed where it will not be affected by draught from
open doors or windows, the airflow from the heater itself, etc.
Electrical connection of original accessories for AW-s models
1. Thermostat R31 (photo 22) with a temperature range of +7 to +30°C and protected to IP20.
One thermostat can control a maximum of three AW-s fan heaters.
2. Thermostat SR121/1 (photo 23) with a temperature range of 0-40°C and protected to IP54.
One thermostat can control a maximum of two AW-s fan heaters.
Photo 22 R31
Photo 23 SR121/1
Photo 18
Photo 19
Photo 20
Photo 21
Содержание AW Series
Страница 34: ...AW 12s 62s 12a 62a 34 Bilaga E Appendix E Anlage E...
Страница 35: ...AW 12s 62s 12a 62a 35 Bilaga F Appendix F Anlage F...
Страница 36: ...AW 12s 62s 12a 62a 36 Bilaga G Appendix G Anlage G...
Страница 37: ...AW 12s 62s 12a 62a 37 Bilaga H Appendix H Anlage H...
Страница 38: ...AW 12s 62s 12a 62a 38 Bilaga I Appendix I Anlage I...
Страница 39: ...AW 12s 62s 12a 62a 39 Bilaga K Appendix K Anlage K...