17
AW DX
Fig. 13
Fig. 14
Fig. 15
Fig. 16
8. The condensate drain has a G1/2” connection, see Fig. 13. If the drain is connected to the floor drain with a hose, no water
seal is required. If the condensate drain is connected directly to the drainage system, a water seal must be used to prevent the
escape of bad odours.
9. The air deflector can be turned by 180° in case the indoor unit is positioned low (at least 850 mm above the floor) or if the air
is to be directed upwards. Loosen the eight screws with a 1/4” hexagon head and turn the air deflector, see Fig. 14.
10. The indoor unit is connected via the control box to 230VAC, see Fig. 15.
To minimise contamination of the heater, the fan should be stopped when there is no need for heating or cooling.
ACCESSORY
An air deflector is available as an accessory for the AW DX, which directs the air to the sides, see Fig. 16.
It is screwed into the of the top and bottom plates with self drilling screws.