16
AW DX
Fig. 7
Fig. 8
Fig. 9
Fig. 10
Fig. 11
Fig. 12
3. Pull off the rubber seal from the connection pipe and protect the sheet against discolouration with a flame retardant, see Fig. 7.
Attention! Make sure the nitrogen can freely exit so that no overpressure occurs during soldering.
4. The sensor for the liquid pipe is installed outside the internal element frame, see Fig. 8.
Use contact paste and straps with metal locking, insulate with insulating tape.
5. Attach the supplied straps in the hole on the inside of the wall bracket where the fan motor cable is routed, see Fig. 9.
6. Fix the motor cable with the straps, see Fig. 10. Then install the control box on the wall.
7. If the control equipment of the outdoor unit is equipped with a separate room sensor, it can be fixed with a smaller
cable tie on the inside of the bracket, see Figs. 11 and 12.