background image

1

CPU-unit

SUPPLY-unit

User manual ALFA-45

 and ALFANET-45

Cool/Defrost thermostat
with Fan control.

VDH doc. 053884

Version: v1.3

Datum: 04-04-2011

Software: ALFA 45 F

Doc: Do053884.wpd

Range: -50/+50

C, per 1

C

* Installation.

The 

ALFA(NET)-45

  consist  of  two  parts,  a  Supply-unit  for  rail-mounting  and  a  CPU-unit  for  front-

mounting (with operation buttons, display). These two units are connected with each other by a cable
with 8-pole data-connector.
On the front of the 

ALFA-45 Modulbox

 

supply-unit

 is shown how sensors and power supply are to

be connected.
After connecting the 

ALFA(NET)-45

 to the power supply, a self test is started. As this test has finished

the measured temperature of the product-sensor appears in the display. 
The Supply-unit has three relay outputs, one for the compressor, one for the fan and one for defrost.
The compressor-relay and the defrost-relay got there own led-indication in the display.
And the 

ALFANET -45

 is by use of the 

ALFANET PC-INTERFACE

 controllable on the PC.

* Control.

The 

ALFA(NET)-45

 thermostat can be controlled by three pushbuttons on the front. These keys are:

 

SET

- view / change of settings.

 

UP

- increase of settings.

 DOWN

- decrease of settings.

Содержание ALFA-45

Страница 1: ...it is shown how sensors and power supply are to be connected After connecting the ALFA NET 45 to the power supply a self test is started As this test has finished the measured temperature of the produ...

Страница 2: ...t cycle the defrost can by manually stopped by pushing the UP key and than the SET key while the UP key is hold Start defrost If there is no defrost cycle the defrost can be started manually by pushin...

Страница 3: ...er P26 1 Startup delay after power failure Offset defrost sensor Fan off delay if parameter P22 1 Readout defrost sensor 1 15 C 50 50 C 50 50 C 15 15 C 0 3 0 99 1 99 Hours 0 99 Minutes 99 99 C 99 99 C...

Страница 4: ...e of the following parameters is set to 1 the fan can be stopped Parameter 19 1 Fan switch differential active The fan is only active when the defrost temperature is parameter 13 C lower then the meas...

Страница 5: ...st is started when the compressor has run for parameter 7 hours after the last defrost Parameter 25 1 The temperature readout on the display is locked during defrost cycle Parameter 26 1 After power u...

Страница 6: ...play of the ALFA NET 45 the following error messages can appear E1 Product sensor error Fatal error display shows E1 and all relays are deactivated accept when parameter 24 is 1 then the compressor an...

Страница 7: ...se see Product sticker Max used power 6 2 VA Fuse No internal fuse present Product sensor SM 811 2m Defrost sensor SM 811 2m Relay Compressor SPST 250V 16A C NO cos phi 1 Relay Defrost SPST 250V 8A C...

Страница 8: ...8 Dimensions CPU unit Dimensions SUPPLY unit Connections...