Series 65
INSTALLATION
980029EB
Edition 2019-10-11
31/103
4.3.2.4
Power and sensor connection (
±
15 VDC sensors) without opt. SPS module external
[653 . . - . . G . - . . . . / 653 . . - . . H . - . . . . versions recommended]
•
VAT fuse recommendation: (a) 5 AF
•
Use shielded sensor cable(s). Keep cable as short as possible, but locate it away
from noise sources.
•
Connect Power supply (+24 / GND) at DA–15 male power connector and Sensors
(0V / + / -) at DA–15 female sensor connector exactly as shown in the drawing
above!
•
Connector: Use only screws with 4–40 UNC thread for fastening the connectors!
Pins 4 and 11 must be
bridged for operation.
An optional switch
would allow for motor
interlock to prevent
valve from moving.
Low range sensor may be
connected to sensor 1 or
sensor 2 input. Do
configuration accordingly.