Servicing
98
11.3.1.
Air filter replacement: Time reset
The air filter must be replaced on every
other servicing. Refer to chapter 11.4.7.
Select
â
Settings
â
Service.
Press the button.
11.3.2.
Checking current sensor values
Check the sensor values (I phase L1,
I phase L2 and I phage L3) for
realistic
values.
Measures in case of value 0:
If one sensor value is approx. 0 although
the phase is currently under load, the
connection between current sensor and
energy storage system may be disturbed.
As necessary, load all phases
separately: Switch on targeted
consumers.
As necessary, check the current flow
through all three phases with a clip-on
ampere meter.
Measures in case of irregular current
sensor values:
Make sure that the connection has a
clockwise phase sequence.
If the current sensor value of one of more
phases is 0 despite loading, check the
connection between the energy storage
system and the current sensor.
As necessary, replace the
connection line (RJ12 cable).
Содержание Pulse neo Series
Страница 1: ...VARTA STORAGE GMBH OPERATING MANUAL VARTA pulse neo...
Страница 2: ...Leerseite Pagina vuota Page blanche Blank page...
Страница 4: ...Leerseite Pagina vuota Page blanche Blank page...
Страница 29: ...General information 29 VARTA pulse neo front view 1 Nameplate 2 ON OFF button 3 Screw positions...
Страница 32: ...General information 32 2 4 2 ID label of battery module 2 4 3 Unlock code label...
Страница 64: ...Installation 64 Three Phase Single Phase Not permitted...
Страница 67: ...Installation 67 All Dimensions in mm Fig 2 Dimensions at the mounting plate...
Страница 145: ...Subject to modification Appendix Appendix 1 Connection diagram of TT system...
Страница 146: ...Subject to modification Appendix 2 Connection diagram of TT system with data logger...
Страница 147: ...Subject to modification Appendix 3 Connection diagram of TN C system...
Страница 148: ...Subject to modification Appendix 4 Connection diagram of TN C system with data logger...