Fault during initialisation
Correct the faults before continuing with initial
commissioning via the web-interface.
LED circle
Colour
Possible cause
Solution
ON/OFF button is
not pressed.
Press the ON/OFF
button
Hood incorrectly
installed
Open hood and install
according to instructions.
White
Fuse not switched-
on
Switch on the fuse.
No AC grid
connection
Check AC grid
connection and establish
as necessary.
Switch defective
Check the switch and
replace as necessary.