
54
Subject to modification! Updated 12/2017
The screws for opening the housing must be accessible from
below. Comply with the min. dimensions in Figure 14: "Dimensions
on mounting plate (
A minimum clearance of 30 cm must be left above the housing. To
ensure that the cooling air can exit the unit unhindered, the min.
clearance of 15 cm to either side must be ensured.
Environmental conditions
8.3.2
The installation location must match a pollution degree 2.
A continuous air exchange, possibly via forced ventilation, e.g.
window, air-conditioning system, ventilation or the like, has always
to be ensured. The distance to the ventilation must be at least
100 cm.
The room temperature must always be between 5
30 °C
(o18 °C), the relative humidity must be < 80%.
Recommendation: well ventilated room without external heat
sources
Sufficient rodent protection must be provided.
Smoking is not allowed at the installation
location.
Содержание VARTA pulse 3
Страница 1: ...Subject to modification Updated 12 2017 Version 01 INSTRUCTION MANUAL VARTA pulse VARTA Storage GmbH ...
Страница 64: ...64 Subject to modification Updated 12 2017 Click the button Send registration now ...
Страница 76: ...76 Subject to modification Updated 12 2017 Figure 14 Dimensions on mounting plate mm ...