Troubleshooting
NB! TROUBLESHOOTING AND REPAIRS MUST ONLY BE PERFORMED BY QUALIFIED
PERSONNEL
ERROR
DISPLAY SHOWING
CAUSE
CHECK / CORRECTION
Boiler «dead»
The boiler lacks of control
voltage
The boiler requires its own
control voltage
Fuse/s for control voltage
broken
Check fuses and replace if
required
No power
Temp 30.0 (80)°C
StepS 0 ( 0)
External start signal missing Check external signal
Temp 30.0 (80)°C
StepE 0 ( 0)
External signal for power
control missing
Check external signal
TempE 30.0 (20)°C
Power 0kW
External signal for
temperature control missing
Check external signal
Temp 0.0 (80)°C
Error Temp
Defect temp. sensor
Change temp. sensor
Boiler stops at
Step 3
(Alarm diode is
flashing)
Temp 30.0 (80)°C
Alarm Power
Safety temp. limiter has
tripped
Reset Safety temp. limiter
(STB) on front panel
Temp 30.0 (80)°C
Alarm Power
Main switch off or broken
fuses
Check switch board/fuses
Replace if required
Little heat
from boiler
Temp 75,5(80)°C
Step 3( 5)
Maximum power limited
from outside
Check external signals from a
central monitoring system
TempU 30.0 (60)°C
Power 120kW
Check if boiler is limited
from outdoor compensator
Check curves for outdoor
compensation
Defect heating elements,
fuses, contactors
Check heating elements, fuses
contactors and replace if
required
STB
– safety
temp. limiter
released
(Display shows
"Alarm Power")
Temp 30.0 (50)°C
Alarm Power
Circulation in boiler
Check pump/valves
Burned contactor
Check contactors and replace if
required
Leakage
Loose screws for heating
element
Tighten screws
Gasket for heating element
Replace if required
Defect heating element
Replace if required