Varmeteknikk AS
Phone +47 23 37 55 00 November 2021
V2
12
Menus
By pressing the arrow (
) button you can scroll through the different menus.
At startup:
EL 15 v1725
El 15 : 15-step controller
V1725: version
Main menu
Temp 60.0 (80)°C
Power 120kW
Step 1 ( 15)+
Step time 40s
Outdoor t. -15°C
Parallel 0°C
(only when outdoor sensor is connected)
In the main menu following adjustments
are available:
- Adjustment of set temperature
- Adjustment (limitation) of max available
steps
- Adjustment of step time
Note!
Short step time will reduce the lifetime
of the contactors.
Service menu
For access to service menu, press and
hold arrow button for min. 5 sec.
Temp 60.0 (80)°C
Power 120kW
Current
0,0(5,0)A
Current marg
1,0A
Power factor
60kW/A
Curve 40°C
Curve min 21°C
(Vises kun når uteføler innkoblet)
Test contactor 0
K1-4 0000 A1
Step time
Service 0
Power IN
OFF
Temp IN
OFF
English
Net 107
Integral.time
600s
Step time out
5