Commissioning 

Note!   BEFORE  SWITCHING  ON  THE  BOILER  CHECK  THE  FOLLOWING: 

-  Check that the water system is completely filled with water. To prevent heating element break  

down make sure there is no air pockets in plant. 

-  Switch on circulating pump and check water flow and direction. 

-  Hydraulic expansion system has to be controlled. Min. pressure, 1bar. 

-  Check for correct supply voltage  

Note!   Before start up, retighten all electrical connections

This appliance is not intended for use by persons (including children) with reduced physical, 
sensory or mental capabilities or lack of experience and knowledge, unless they have been 
given supervision or instruction concerning use of the appliance by a person responsible for 
their safety. 

Children should be supervised to ensure that they do not play with the appliance.  

Start up 

Switch on the boiler by using the ON/Off-switch on the front panel. Display will after a few seconds 
show actual water temp., preset temp. in brackets. The line below shows connected power. Boiler  
will now step by step increase power to obtain preset temperature.  

The temperature is factory set at 80 °C, and step time is set to 40 sec. Unless corrections of preset 
temperature or step time are required, no further adjustments are needed.  

Note! If boiler is controlled by external signals, missing signal can prevent boiler from 
running. 

Temperature controller

The boiler is equipped with a 7-steps electronic temperature controller located in front of the boiler. 
All settings can be done at the front. The controller has a proportional and integrating control and is 
designed to maintain constant boiler temperature. Temperature range is from 5 - 95°C in steps by  
1 °C. 3 relays control the power contactors which are connected in a binary order. This gives a high 
degree of reliability  

If a failure occurs, an alarm diode starts flashing. Type of failure will be shown in display and could  
be: 

Don’t switch on the boiler if there is a possibility that the water in boiler 
is frozen. 

frozen

Содержание MB 35

Страница 1: ...Installation operating servicing MB boilers 35 45 60 75 90 105 120 140 150kW...

Страница 2: ...elements 4 4 7 7 7 Temp controller steps 7 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65 1...

Страница 3: ...A 217A Number of elements 7 7 7 8 Temp controller steps 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65...

Страница 4: ...k no 4 MB 35 150kW 590 690 NB Fri h yde over kjel ca 100cm 1 2 3 4 5 6 7 8 9 10 1 Temp controller 2 Safety temp limiter 3 ON OFF switch 4 Contactors 5 Fuses circuit breakers 6 Bus bars for connecting...

Страница 5: ...rt up 7 Temperature controller 7 Settings 8 Additional functions 9 Remote control Boiler Start stop 10 Temperature control 10 Power control 10 Monitoring Operation signal 11 Failure signal 11 Output s...

Страница 6: ...operating pressure of the boiler To avoid damage a pipe pointing down towards the floor should be fixed to the pressure safety valves Connection NOTE INSTALLATION MUST ONLY BE EXECUTED BY QUALIFIED P...

Страница 7: ...the front panel Display will after a few seconds show actual water temp preset temp in brackets The line below shows connected power Boiler will now step by step increase power to obtain preset temper...

Страница 8: ...set temperature is factory set to 80 C If correction is needed do the following Press or button to set desired temperature Then press enter to save new value Step time Step time is adjustable between...

Страница 9: ...hole step base Limitation can be done in the menu or on a potentiometer located on the PCB Limitation in menu Enter Step mode and press button Choose number of power steps and then press E button to s...

Страница 10: ...ed in service menu see page 12 Temp IN must be set in ON position Press button twice and then E to enter new value Temp IN ON Press menu button twice to return to Temp Power mode When signal is activa...

Страница 11: ...sor broken or control voltage 190V Connection on terminal 5 6 Type of error is shown in display Output 0 10V DC signals External power indication 0V 0kW 10V Max kW terminal 36 39 External temp indicat...

Страница 12: ...ppears only if outdoor sensor is connected Settings in main menu Desired temperature Number of power steps Step time Service menu To get access to service menu press and hold menu button for more than...

Страница 13: ...or burning Any noise from con tactor indicates wear and requires a thorough check Be aware that burnt contactors may cause major damage Electrical connections Retighten all electrical connections on...

Страница 14: ...g box mounted on left side without moving transformer Transformer must be mounted on same side as connecting box Temp 30 0 80 C Alarm Power Safety temp limiter has tripped Reset safety temp limiter ST...

Страница 15: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 15 Circuit diagram MB 35 150kW...

Страница 16: ...MB 35 150kW Apparatplate 400V MB 105kW 120kW 140kW Apparatplate 400V MB 60kW 75kW 90kW Apparatplate 400V MB 35kW 45kW E1 E2 E3 E4 E1 E2 E3 E4 E5 E6 E7 E1 E2 E3 E4 E5 E6 E7 Apparatplate 400V MB 150kW...

Страница 17: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 17 Temp controller terminals...

Страница 18: ......

Страница 19: ...or AF26 41 175 48 3 1 3 1 2 3 1 3 4 1 1 1 1 2 Contactor AF30 41 175 56 1 1 1 3 1 Contactor A50 41 147 56 1 3 2 3 3 3 3 3 Contactor A63 41 148 16 3 Contactor A75 41 148 46 3 Contactor A95 41 149 36 2 C...

Страница 20: ......

Страница 21: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 21 Notes...

Отзывы: