Varmeteknikk MB 35 Скачать руководство пользователя страница 10

Varmeteknikk AS

August 2017     e-mail:  [email protected]

10

Remote control by external signals 

The boiler offers several possibilities for remote control. With a start/stop signal (potential free),  
boiler can be connected/disconnected from running. Maximum output or preset temperature  
can be controlled by a 0-10V DC signal.  

Remote start/stop of boiler

Boiler can be switched On/Off by an external signal. Before connecting signal, remove bridge on 
terminal 1 & 2, see next page. If start/stop-signal is connected and boiler gets start signal, display 
shows: 

Temp     47.0 (75)°C     
Step    

   0 (30)

Temperature control by 0-10V signal 

Desired temperature can be controlled by a 0-10V DC signal. 0V = 20°C, 10 V = 120

C°. Normal  

temp. range is from 20 – 95°C, equivalent to 0 - 8,5V. Connection on terminal 30(-) and 31( +)   
on PCB (see page 17). Signal must be activated in service menu, see page 12.  

"Temp IN"

  must  

be set in

 ”ON”

  position. Press 

button twice and then 

to enter new value. 

Temp IN 

                            ON 

Press menu button twice to return to 

"Temp/Power" 

mode. When signal is activated display  

shows:

TempE   47.0(75)°C     
Power             60kW

Note!

  When desired boiler temperature is controlled by a external 0-10V signal, internal set point  

must be set as high as boiler should work. Internal thermostat is now working as a maximum  
thermostat and limit the temperature. This must be done before signal is activaded.

Power control by 0-10V signal 

Boiler output can be controlled by a 0 -10V DC signal. 0V = 0 step, 10V = all steps (15/30). Con- 
nection on terminal 29(+) and  30(-) on PCB (see page 17). Signal must be activated in service  
menu, see page 12.  "

Power IN

" must be set in "

ON"

 position.  Press 

button twice and then   

to enter new value. 

Power  IN                         
                          ON

Press menu button twice to return to 

"Temp/Power" 

mode. When signal is activated display  

shows:

StepE              3 ( 7)       
Step time           40s

Temp      47.0 (75)°C  

Step S    

   0 (  0)

If start signal is missing, 
display shows

Содержание MB 35

Страница 1: ...Installation operating servicing MB boilers 35 45 60 75 90 105 120 140 150kW...

Страница 2: ...elements 4 4 7 7 7 Temp controller steps 7 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65 1...

Страница 3: ...A 217A Number of elements 7 7 7 8 Temp controller steps 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65...

Страница 4: ...k no 4 MB 35 150kW 590 690 NB Fri h yde over kjel ca 100cm 1 2 3 4 5 6 7 8 9 10 1 Temp controller 2 Safety temp limiter 3 ON OFF switch 4 Contactors 5 Fuses circuit breakers 6 Bus bars for connecting...

Страница 5: ...rt up 7 Temperature controller 7 Settings 8 Additional functions 9 Remote control Boiler Start stop 10 Temperature control 10 Power control 10 Monitoring Operation signal 11 Failure signal 11 Output s...

Страница 6: ...operating pressure of the boiler To avoid damage a pipe pointing down towards the floor should be fixed to the pressure safety valves Connection NOTE INSTALLATION MUST ONLY BE EXECUTED BY QUALIFIED P...

Страница 7: ...the front panel Display will after a few seconds show actual water temp preset temp in brackets The line below shows connected power Boiler will now step by step increase power to obtain preset temper...

Страница 8: ...set temperature is factory set to 80 C If correction is needed do the following Press or button to set desired temperature Then press enter to save new value Step time Step time is adjustable between...

Страница 9: ...hole step base Limitation can be done in the menu or on a potentiometer located on the PCB Limitation in menu Enter Step mode and press button Choose number of power steps and then press E button to s...

Страница 10: ...ed in service menu see page 12 Temp IN must be set in ON position Press button twice and then E to enter new value Temp IN ON Press menu button twice to return to Temp Power mode When signal is activa...

Страница 11: ...sor broken or control voltage 190V Connection on terminal 5 6 Type of error is shown in display Output 0 10V DC signals External power indication 0V 0kW 10V Max kW terminal 36 39 External temp indicat...

Страница 12: ...ppears only if outdoor sensor is connected Settings in main menu Desired temperature Number of power steps Step time Service menu To get access to service menu press and hold menu button for more than...

Страница 13: ...or burning Any noise from con tactor indicates wear and requires a thorough check Be aware that burnt contactors may cause major damage Electrical connections Retighten all electrical connections on...

Страница 14: ...g box mounted on left side without moving transformer Transformer must be mounted on same side as connecting box Temp 30 0 80 C Alarm Power Safety temp limiter has tripped Reset safety temp limiter ST...

Страница 15: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 15 Circuit diagram MB 35 150kW...

Страница 16: ...MB 35 150kW Apparatplate 400V MB 105kW 120kW 140kW Apparatplate 400V MB 60kW 75kW 90kW Apparatplate 400V MB 35kW 45kW E1 E2 E3 E4 E1 E2 E3 E4 E5 E6 E7 E1 E2 E3 E4 E5 E6 E7 Apparatplate 400V MB 150kW...

Страница 17: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 17 Temp controller terminals...

Страница 18: ......

Страница 19: ...or AF26 41 175 48 3 1 3 1 2 3 1 3 4 1 1 1 1 2 Contactor AF30 41 175 56 1 1 1 3 1 Contactor A50 41 147 56 1 3 2 3 3 3 3 3 Contactor A63 41 148 16 3 Contactor A75 41 148 46 3 Contactor A95 41 149 36 2 C...

Страница 20: ......

Страница 21: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 21 Notes...

Отзывы: