Varmeteknikk AS

August 2017     e-mail:  [email protected]

14

Troubleshooting  

NOTE!  TROUBLESHOOTING  MUST  ONLY  BE  EXECUTED  BY  QUALIFIED  PERSONNEL 

  FAILURE      

  DISPLAY TEXT 

POSSIBLE CAUSE OF TROUBLE                        

CONTROL /REPAIR 

BOILER  
”dead” 

Control voltage missing 

Boiler needs separate 
control voltage 

Fuse/s for control voltage broken 

Check fuses and replace if 
required 

NO POWER  

Temp      30.0 (80)°C     
StepS          0 (  0) 

External start signal missing 

Check external signal. (See 
terminal 1& 2 on –X1)   

Temp      30.0 (80)°C     
StepE          0 (  0) 

External signal for power control 
missing 

Check external signal  

TempE    20.0 (20)°C     
Power               0kW    

External signal for temperature  
control missing 

Check external signal 

Temp        0.0 (80)°C     
Error   Temp    

Defect  temp.sensor 

Change  temp.sensor and 
Replace if required 

BOILER 
STOPS   AT 
STEP 3 

(Alarm diode is 
flashing) 

Temp      30.0 (80)°C     
Alarm Power    

Connecting box mounted  on left 
side without moving transformer 

Transformer must be 
mounted on same side as 
connecting box 

Temp      30.0 (80)°C     
Alarm Power             

Safety temp.limiter  has tripped 

Reset safety temp.limiter 
(STB) on front panel 

Temp      30.0 (80)°C     
Alarm Power    

Main switch off or  broken fuses    

Check switch board/fuses 
Replace if required 

LITTLE HEAT 
FROM BOILER

Temp      50.0 (80)°C   
Step             4 (  4)   

Maximum power  limited 
from outside 

Check external signals from 
a central monitoring system 

TempU   30.0 (30)°C     
Power               0kW 

Check if boiler is limited from 
outdoor compensator 

Check curves for outdoor 
compensation 

 

Defect heating elements, 
fuses, contactors        

Check heating elements, 
fuses, contactors and 
replace if required 

STB,  safety 
temp.limiter 
released 

(Display shows 
"Alarm Power") 

Temp       30.0 (80)°C     
Alarm Power    

circulation in boiler 

Check pump/valves 

Burned contactor 

Check contactors and 
replace if required 

LEAKAGE 

Loose screws for heating element 

Tighten screws 

Gasket for heating element 

Replace if required  

Defect  heating element 

Replace if required 

Содержание MB 35

Страница 1: ...Installation operating servicing MB boilers 35 45 60 75 90 105 120 140 150kW...

Страница 2: ...elements 4 4 7 7 7 Temp controller steps 7 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65 1...

Страница 3: ...A 217A Number of elements 7 7 7 8 Temp controller steps 7 7 7 7 Temp range 30 95 C 30 95 C 30 95 C 30 95 C Water contents liters 75 75 75 75 Tube connections Outlet inlet DN65 16 DN65 16 DN65 16 DN65...

Страница 4: ...k no 4 MB 35 150kW 590 690 NB Fri h yde over kjel ca 100cm 1 2 3 4 5 6 7 8 9 10 1 Temp controller 2 Safety temp limiter 3 ON OFF switch 4 Contactors 5 Fuses circuit breakers 6 Bus bars for connecting...

Страница 5: ...rt up 7 Temperature controller 7 Settings 8 Additional functions 9 Remote control Boiler Start stop 10 Temperature control 10 Power control 10 Monitoring Operation signal 11 Failure signal 11 Output s...

Страница 6: ...operating pressure of the boiler To avoid damage a pipe pointing down towards the floor should be fixed to the pressure safety valves Connection NOTE INSTALLATION MUST ONLY BE EXECUTED BY QUALIFIED P...

Страница 7: ...the front panel Display will after a few seconds show actual water temp preset temp in brackets The line below shows connected power Boiler will now step by step increase power to obtain preset temper...

Страница 8: ...set temperature is factory set to 80 C If correction is needed do the following Press or button to set desired temperature Then press enter to save new value Step time Step time is adjustable between...

Страница 9: ...hole step base Limitation can be done in the menu or on a potentiometer located on the PCB Limitation in menu Enter Step mode and press button Choose number of power steps and then press E button to s...

Страница 10: ...ed in service menu see page 12 Temp IN must be set in ON position Press button twice and then E to enter new value Temp IN ON Press menu button twice to return to Temp Power mode When signal is activa...

Страница 11: ...sor broken or control voltage 190V Connection on terminal 5 6 Type of error is shown in display Output 0 10V DC signals External power indication 0V 0kW 10V Max kW terminal 36 39 External temp indicat...

Страница 12: ...ppears only if outdoor sensor is connected Settings in main menu Desired temperature Number of power steps Step time Service menu To get access to service menu press and hold menu button for more than...

Страница 13: ...or burning Any noise from con tactor indicates wear and requires a thorough check Be aware that burnt contactors may cause major damage Electrical connections Retighten all electrical connections on...

Страница 14: ...g box mounted on left side without moving transformer Transformer must be mounted on same side as connecting box Temp 30 0 80 C Alarm Power Safety temp limiter has tripped Reset safety temp limiter ST...

Страница 15: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 15 Circuit diagram MB 35 150kW...

Страница 16: ...MB 35 150kW Apparatplate 400V MB 105kW 120kW 140kW Apparatplate 400V MB 60kW 75kW 90kW Apparatplate 400V MB 35kW 45kW E1 E2 E3 E4 E1 E2 E3 E4 E5 E6 E7 E1 E2 E3 E4 E5 E6 E7 Apparatplate 400V MB 150kW...

Страница 17: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 17 Temp controller terminals...

Страница 18: ......

Страница 19: ...or AF26 41 175 48 3 1 3 1 2 3 1 3 4 1 1 1 1 2 Contactor AF30 41 175 56 1 1 1 3 1 Contactor A50 41 147 56 1 3 2 3 3 3 3 3 Contactor A63 41 148 16 3 Contactor A75 41 148 46 3 Contactor A95 41 149 36 2 C...

Страница 20: ......

Страница 21: ...Varmeteknikk AS August 2017 e mail post varmeteknikk no 21 Notes...

Отзывы: