STAGE 2 RELATIVE SET POINT
The stage 2 relative set point establishes the
temperature at which stage timer 2 begins to
operate. The value is a temperature
difference
from the main set point.
The stage 2 RSP is adjusted in 0.5-degree
increments from a minimum setting of 0.0°F
(0.0°C) to a maximum setting of 18.0°F (10.0°C).
Adjusting the stage 2 RSP:
•
rotate the Selector dial to position (5),
•
rotate the Adjuster dial counter clockwise to
decrease the relative set point, and
clockwise to increase it.
The stage 2 RSP is displayed on the MST-2B.