Page 43
HIGH TEMPERATURE ALARM
This function establishes the temperature
difference above the main set point that the
room can reach before a high temperature
alarm is triggered. When a high temperature
alarm occurs, an alarm contact is activated
and the alarm LED segment lights up on the
panel.
The high temperature alarm is adjusted in 0.5
degree increments from a minimum setting of
0.0°F (0°C) to a maximum setting of 32.0°F
(18.0°C).
Adusting the low temperature alarm
setting:
•
rotate the Selector dial to position (12);
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode;
•
rotate the Selector dial to position (10);
rotate the Adjustor dial counterclockwise to
decrease the setting, clockwise to increase it.
The high temperature alarm setting is
displayed on the front panel.
Alarm
CHAPTER 3 - USER’S GUIDE
www.monitrol.com
Содержание ECS-4+
Страница 1: ...ECS 4 USER S GUIDE www monitrol com ...
Страница 8: ...Page 8 ECS 4 www monitrol com ...
Страница 17: ...Page 17 Figure 5 Main Board Terminal block switches fuses and ground CHAPTER 2 INSTALLATION www monitrol com ...
Страница 18: ...Page 18 ECS 4 Figure 6 Recommended control backup www monitrol com ...
Страница 48: ...MAV ECS4 V2 1 July 2001 www monitrol com ...