Page 39
This function establishes the temperature
difference
above the main set point that the room can reach
before a high temperature alarm is signalled. When a
high temperature alarm occurs an alarm contact is acti-
vated and the alarm LED lights up on the front panel.
The high temperature alarm is adjusted in 0.5 degree
increments from a minimum setting of 0°F (0°C) to a
maximum setting of 32.0°F (18.0°C)
Adjusting the high temperature alarm:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and forth to enter
secondary function mode,
•
rotate the Selector dial to position (11),
•
rotate the Adjustor dial counterclockwise to decrease
the setting, clockwise to increase it.
The high temperature alarm setting is displayed on the
ECS.
CHAPTER 3 - USER’S GUIDE
HI TEMP ALARM
11
www.monitrol.com
Содержание ECS-2M
Страница 8: ...Page 8 ECS 2M www monitrol com ...
Страница 19: ...Page 19 Fig 7 Recommended control backup CHAPTER 2 INSTALLATION www monitrol com ...
Страница 21: ...Page 21 CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 41: ...Page 41 APPENDIX www monitrol com ...
Страница 42: ...Page 42 ECS 2M www monitrol com ...
Страница 48: ...MAV ECS 2M Ver 1 0 June 5 2001 www monitrol com ...