Page 11
2.3.2 - Software Settings Switch
This switch is located behind the control panel faceplate
and adjusts the following options.
1
2
3
4
Switch
1
Selects between a Fahrenheit or Celsius
display on the front panel.
Switch 2 Locks/unlocks user settings. All settings except
for main set point, record low, and record high
are locked while this switch is off.
Switch 3 Selects between a Heater or Fan control on
Stage two of the control panel.
Switch 4 To connect a humidity probe, DIP switch #4
must be ON.
2.4 CONNECTION PROCEDURE
For the connection procedures which follow refer to
Figures 1 to 3.
2.4.1 - Input power
Use a screwdriver to remove cable knock-outs for the
installation of cabling to the control panel.
2.4.1.1 - 115 VAC
Make sure that the line voltage selector switch is set to
115 VAC
. Connect the power cable to terminals 5 and 6 on
the main (bottom) board, connect the ground wire to
terminal 7 on the main board .
OFF
ON
Fahrenheit
Settings locked
Stage 2 = Heat
Not used
Celsius
Setting unlocked
Stage 2 = Fan
Relative Humidity
Do not apply power to the control panel until all
connections have been completed!
CHAPTER 2 - INSTALLATION
OFF ON
www.monitrol.com
Содержание ECS-2M
Страница 8: ...Page 8 ECS 2M www monitrol com ...
Страница 19: ...Page 19 Fig 7 Recommended control backup CHAPTER 2 INSTALLATION www monitrol com ...
Страница 21: ...Page 21 CHAPTER 3 USER S GUIDE www monitrol com ...
Страница 41: ...Page 41 APPENDIX www monitrol com ...
Страница 42: ...Page 42 ECS 2M www monitrol com ...
Страница 48: ...MAV ECS 2M Ver 1 0 June 5 2001 www monitrol com ...