DIN Low Voltage Output Station — MODEL: LVOS-0-10-PWM-DIN 

page 1 of 2 

I N S T A L L A T I O N 

 

V A N T A G E C O N T R O L S . C O M  

V A N T A G E   I N S T A L L   G U I D E S

 

2168 West Grove Parkway, Suite 300, Pleasant Grove, UT.  84062   USA 
Telephone:  801 229-2800 

 Fax:  801 224-0355 

DIN Low Voltage Output Station — MODEL: LVOS-0-10-PWM-DIN 

 

Overview 
The Vantage LVOS-0-10-PWM-DIN has eight low voltage outputs. 
Loads 1-4 may be configured as 0-10V (analog) or PWM (source 
only) loads. Loads 5-8 are 0-10V, analog only.  

 
Features 

 

8, independent 0-10V low voltage outputs 

 

Outputs 1-4 can be configured as PWM or 0-10V 

 

Manual control and LED status for all 8 LV outputs on front 

 

High resolution performance when dimming 

 

Communicates via station bus 

 

Assembled in a 9 unit DIN case 

 

Override switch for ON and OFF states of all loads 

 

CE Certification / UL 

 
Station Specifications 

General

 

Dimensions, HWD 

85.7mm x 157.2mm x 61.9mm

3.38” x 6.19” x 2.44” 

Weight 237g 

/ 8.36oz. 

LED Indicators 

Microprocessor status, configuration, loads

LED on loads 1-4: Red = 0-10 / GREEN = 

PWM 

Ambient 

Operating 

Temperature 

32-104°F / 0-40°C 

Relative Humidity 

Maximum 90%, non-condensing

Cooling Convection 

Firmware 

Upgradeable via station bus

Manual Control 

Overlay with control/status for each output

FreeRTOS 

Real-time scheduling provided by 

FreeRTOS (www.freertos.org)

Compliance  

UL • CUL • RoHS• CE • FCC (see Certifications)

DC Input – Power Supply 

Input Voltage 

13.8 – 36VDC 

Input Power Draw 

<15W 

Connection Type 

0.20” pitch removable plug

Connection Rating 

300V 10A 

Input / Output Connections (Low Voltage) 

Station Bus 
Connection 

24V / 36V Station Bus 

Station Bus Wire 

Specification 

2C, 16AWG / 1.31mm2, twisted, non-

shielded, <30pF per foot. Separate a 

minimum of 12" / 30.5cm from other parallel 

communication and/or high voltage runs.

Station Wiring  

Daisy-chain/Star/Branch

Station Count 

0.35W on IC-24 / 0.55W on IC-36

Auxiliary Inputs 

4 Dry Contacts, (3 and 4 may be used for an 

IR Receiver and Light Sensor respectively)

Override Inputs 

Yes – All ON or All OFF contacts

Low Voltage Output: 0-10V

 

Specification 

IEC 60929 Annex E 

Number of 

outputs 

Output 

0-10V @ 100mA sink or source

External source 

voltage 

Typical 10V / Maximum 20V 

Loads Per Output 

50@ 2.0mA per load (typical)

Resolution >1024 

steps 

Connection type 

0.20” pitch removable plug

Connection rating 

300V 10A 

Low Voltage Output: PWM

 

Specification 

IEC 60929 Annex E 

Number of 

outputs 

Output voltage 

12V (source only) 

Output current 

100mA per channel, 400mA total

Loads Per Output 

50@ 2.0mA per load (typical)

Resolution > 

1024 

steps 

Duty cycle 

Variable 0% to 99.9% 

Frequency 760Hz 

Connection type 

0.20” pitch removable plug

Connection rating 

300V 10A 

Protection 

 

DC input, over current protection 

 

 
 
 
 
 
 
 

PTC fuse (self resetting) 

 
 
 
 

 
 

 

Low voltage 0-10V output over 

current protection 

 

 

Low voltage PWM output over 

current protection 

 

Certifications

CE, 

FCC 

Part 15, 

Sub-

Part B 

EN55022 Radiated / Conducted emissions 
EN55024 61000-4-2 ESD immunity 
EN55024 61000-4-3 Radiated immunity 
EN55024 61000-4-4 Fast transient immunity 
EN55024 61000-4-5 Surge immunity 
EN55024 61000-4-6 Conducted immunity 
EN55024 61000-4-8 Magnetic field immunity 
EN55024 61000-4-11 Voltage dips/interruption immunity 
61000-3-2 Harmonics current emissions 
610000-3-3 Flicker emissions 

 
Load Configurations 
Setting up the 
load 
configurations, 
as shown at 
right, is done 
in Design 
Center 
software. 
Only loads 1-4 
may be 
configured as 
PWM. Set all 
four loads as 
PWM or in 
sets of two, 
e.g., loads 1&2, 
or loads 3&4.  
 
Low Voltage 
Outputs, 0-
10V (analog) 
Low Voltage Controls 1-8 and Ground are used to control devices 
that work with an analog 0-10V signal. Ground provides the 
negative reference for the output voltages. All Grounds are 
connected internally to each other. Each control output, 1-8 can 
sink or source 0-100mA at any voltage from 0-10VDC. The load 
level sets the percentage between the minimum and maximum 
voltage that is selected for that load. LED load indicators are 

red

 

for all loads in 0-10V mode; loads 5-8 are only 0-10V. 
 
PWM Outputs, 12V (Source) 
Low voltage outputs 1-4 may be configured as PWM (Pulse Width 
Modulation). Only use combinations 1-4, 1&2, or 3&4 as illustrated 
for PWM outputs. PWM Duty Cycles are programmed using Power 
Profiles from 0%-

Minimum On

 to 100%-

 Maximum On

 (99.9% 

actual). The load level is a percentage between the minimum and 
maximum duty cycle (Power Profile Minimum On and Maximum 
On). The output can be reversed in Design Center through the 
Power Profile. For example, a 0% duty cycle can either be load ON 
or load OFF. LED load indicators 1-4 are 

green

 for loads in PWM 

mode. 
 

NOTE: Loads 1 – 8, Low Voltage outputs, should be 
limited to 250 feet / 76.2 meters for each wire run, using 
a minimum of 18AWG / 0.823mm2 gauge wire. All 
connections use 4.4 inch pound torque. Stranded wire 
recommended. 

 
Software/Firmware 
Design Center Software version 3.x or higher and accompanying 
Firmware, are compatible. For new projects it is recommended that 
software and firmware be kept to the most current release. 
 
Power Profiles / Power Outages 
The Dimmer Station stores Power Profile configuration data locally 
so that it will continue to operate correctly if communication with 
the system is lost. This information includes: load profile-duty cycle 
settings, last load level, and PWM or 0-10V power profiles. If a 
station is moved to a new location or if the load type connected is 
changed from a 0-10V load to a PWM load, or vice-versa, 
remember to change the load type in Design Center, to avoid 
unwanted results. Before testing new load type via the local 
buttons on the front, program the station to the system so the new 
load type is active in the station’s output. 
If a power outage occurs, when power is restored the station will 
return the loads to the last load level with all profiles at there last 
known settings. This occurs whether or not the station is 
connected to the Controller. 
 
Actuator Buttons 
The actuator buttons on the front of the station are for local 
control only and are not programmable through Design Center 
software. In 

Diagnostics

, these eight buttons and the four dry-

contacts have not been implemented in 

Button Press Monitor