Testing and Trouble Shooting
BATTERY EQUALIZER OWNER’S MANUAL
9
B), and less than 0.05 VDC between the Equalizer' s GND terminal and the battery ground terminal
(Battery A negative terminal that is connected to chassis ground). In most installations, the Battery
Equalizer' s terminals are wired directly to the battery terminals to prevent voltage loss that could occur in
switch contacts, connections, and long wire runs. Since the equalizer can be operated in temperatures up
to 71º or 75º C, use wire rated at least 90º C. See Wire and Fuse Size Chart.
Wire and Fuse Size Chart
Max wire length, in feet, between Equalizer and battery to keep voltage drop under 0.1
volt. The chart assumes wire carries no other load and wire temperature is below 80º C.
60-60
60-80
60-100
2 x 60-100
65-60
65-80
65-100
2 X 65-100
Wire
Size
AWG
Ring Terminal
Molex or UL
recognized
equal
60-10
60-20
60-50
66-60
66-80
66-100
2 X 66-100
#14
191930072
3.2
XXX
XXX
XXX
XXX
XXX
XXX
#12
191930134
5.0
2.5
XXX
XXX
XXX
XXX
XXX
#10
191930134
7.7
3.8
XXX
XXX
XXX
XXX
XXX
#8
191930157
12.8
6.4
2.6
2.1
XXX
XXX
XXX
#6
191930251
19.4
9.7
3.9
3.2
2.4
XXX
XXX
#4
191930278
35.2
17.6
7.0
5.9
4.4
3.5
XXX
#2
191930309
51.9
26.0
10.4
8.7
6.5
5.2
2.6
#1
191930333
65.4
32.7
13.1
10.9
8.2
6.5
3.3
#1/0
191930333
82.9
41.4
16.6
13.8
10.4
8.3
4.1
#2/0
191930346
105.5
52.7
21.1
17.6
13.2
10.5
5.3
Fuse F1
20 amp
30 amp
80 amp
80 amp
100 amp
125 amp
250 amp
Fuse F2
10 amp
15 amp
35 amp
40 amp
50 amp
80 amp
150 amp
Crimp the ring terminals using
Molex
tool 192840002 (14ga), 192840001 (10 -12ga), 192840035 (2 - 8ga) (phone
813-521-2700) and
AC Terminal
tool model 0280 (6 ga and larger) (phone 614-868-9828).
___________________________________________________________________
Testing and Troubleshooting
All Vanner equalizers fall into one of three distinct families. The three families operate differently and
must be tested differently. The following three test procedures apply
only
to the equalizer family listed.
Before testing the equalizer, be sure all battery connections are good and that fuses F1 and F2 are good.
CAUTION
Servicing of electrical systems should only be performed by trained and qualified technical personnel.
Equipment Required
VoltMeter having 0.01 volt resolution. (Fluke Model 87 Multimeter recommended).
Clamp-on amp meter (Fluke Model 36 Clamp-on Meter recommended).
Vanner Repair Service
Vanner offers a quick turn around factory repair service for Family 1 and Family 2 models. (Family 3, 4
and 5 models are non-repairable.) Send the unit to the address below with a note instructing us to repair
it. Include your name, phone number, shipping address (not a P.O. Box Number), and your purchase
order number.