Vanner VoltMaster  60-100 Скачать руководство пользователя страница 14

 !"#$%$%&'(

 !"#$%$%&'(

 Incorporated

                               

Testing and Trouble Shooting

BATTERY EQUALIZER                                                                     OWNER’S MANUAL

14

5.

Subtract Battery A voltage from Battery B voltage and compare readings.

Voltage Comparison

Indicator

Light

Equalizer Status

a.

Battery A is lower than Battery B  but
within 0.05 volt.

OFF

OFF

Stand-by Mode.

The  equalizer  will  not  turn  ON  until  Battery  A  is
lower than Battery B by more than 0.05 volts.

b.

Battery  A  is  lower  than  Battery  B  by
0.05 to 0.10 volts.

ON

ON

Normal Operating Mode

c.

Battery  A  is  lower  than  Battery  B  by
more than 0.10 volts

ON

ON

Self-Protection Mode due to  Overload
Condition. See below.

d.

Battery  A  is  lower  than  Battery  B  by
more than 0.10 volts

OFF

OFF

The 

Equalizer  is 

not  functioning

properly.

e.

Battery A is higher than Battery B

Abnormal condition. Suspect Battery B is defective or a 12 volt load
is connected to Battery B.

Overload Condition

 on Family 3, Family 4 and Family 5 Equalizers

An overload condition exists when the 12 volt loads exceed the equalizer’s rated capacity. The overload
condition will not damage the equalizer but may cause damage to the batteries.

During  the  overload,  the  equalizer  output  is  limited  by  internal  protection  circuits  to  its  Rated  Output
Amps.  The  12  volt  amps  exceeding  the  equalizer  output  are  drawn  from  Battery  A  which  will  begin  to
draw  the  batteries  out  of  balance.  The  equalizer  full  Rated  Output  Amps  are  maintained  as  long  as
Battery  A  and  Battery  B  remain  balanced  within  0.10  volt.  The  internal  protection  circuits  will  reduce
equalizer  output  as  the  batteries  become  further  out-of-balance.  If  Battery  A  voltage  falls  below
approximately 8 volts the equalizer will shut itself OFF.

To  correct  the  overload  condition  the  12  volt  load  must  be  reduced  or  the  equalizer  capacity  must  be
increased.

Trouble Shooting an Engine No-Start Situation

Situation:
A coach has dead batteries and won’t start while jump starting. The coach is equipped with a 24 volt
starting and charging system, a 12 volt electronic diesel engine control, a Family 3, 4 or 5 Equalizer, and
a moderate 12 volt load which cannot be turned OFF. The coach sits for several days and the batteries
run completely dead. During jump starting the engine cranks but does not start due to low voltage on the
12 volt supply. Electrical testing reveals there is no 12 volt output from the equalizer while jump starting
even though the equalizer separately tests OK.

Cause:
The 12 volt load which could not be turned OFF first ran both batteries down until the equalizer shut itself
OFF due to low voltage. (Family 3, 4 and 5 Equalizers will shut OFF if system voltage falls below 16 volts
or if voltage on either battery falls below 8 volts.) Then Battery A alone was drained to near zero volts.
As the bus is being jumped, 12 volt loads hold Battery A voltage too low for the equalizer to turn ON and
Battery A is too weak to support the 12 volt electronic engine control.

Solution:
Turn OFF all 12 volt loads (turning the battery disconnect switch OFF may accomplish this). Connect the
jumper cables but do not crank the engine for two or three minutes or until the equalizer indicator light has
turned  ON  which  means  the  equalizer  is  ON.  (Both  batteries  must  rise  above  8  volts.)  The  battery
disconnect switch can then be turned ON and the bus should have adequate 12 volt power to start.

Содержание VoltMaster 60-100

Страница 1: ...ly 4 Family 5 60 10B 60 100C 60 60 65 60 66 60 60 20A 60 100D 60 60M 65 60M 66 80 60 50A 60 100E 60 80 65 80 66 100 60 50E 60 100 65 100 60 50M Table of Contents Introduction 2 Specifications 3 Theory...

Страница 2: ...tery Equalizer connects to the 24 volt 12 volt and ground terminals of the battery system When the 12 volt loads require power the Battery Equalizer ensures that the current is taken equally from both...

Страница 3: ...unting Location Mount on a flat surface close to the batteries to allow short cable runs Vertical mounting with terminals down is recommended Location should be protected from battery acid and gases 2...

Страница 4: ...the voltage balance and therefore the charge acceptance rate of each battery Family 3 and Family 4 Equalizers hold Battery A and B voltages to within 0 05 volts under light loads and to within 0 1 vo...

Страница 5: ...ng small adjustments to keep the batteries in balance Scenario 2 Both 24 volt and 12 volt loads present alternator is OFF The Battery Equalizer will insure that both batteries will discharge at the sa...

Страница 6: ...CH 24V ALT _ 24V VANNER Battery Equalizer 12V GND 12V Battery B 12V Battery A 12V 12 Volt Loads VANNER DC to AC Inverter 120VAC To AC Loads 24 Volt Loads 24V F2 F1 MARINE ENGINE BATTERY SYSTEM HOUSE B...

Страница 7: ...aining batteries or flammable materials Safety goggles should always be worn when working near batteries Mounting Location The Equalizer may be mounted in any orientation however the recommended orien...

Страница 8: ...ttery Disconnect Switch 24V VANNER Battery Equalizer 12V GND 12V Battery B 12V Battery A 12V 12 Volt Loads Radio 24 Volt Loads 24V 24V ALT _ HIGH CURRENT DIODE BATTERY DISCONNECT SWITCH F2 F1 The syst...

Страница 9: ...7 13 1 10 9 8 2 6 5 3 3 1 0 191930333 82 9 41 4 16 6 13 8 10 4 8 3 4 1 2 0 191930346 105 5 52 7 21 1 17 6 13 2 10 5 5 3 Fuse F1 20 amp 30 amp 80 amp 80 amp 100 amp 125 amp 250 amp Fuse F2 10 amp 15 a...

Страница 10: ...same 12 volt lamp between the 12 and GND terminals of the Equalizer The lamp should light and stay lit If the lamp does not light the light then goes out or the light dims the Equalizer requires repa...

Страница 11: ...occur during bus maintenance it is recommended that the service personnel verify the circuit breaker is IN before releasing the bus for service and the tour bus operator do the same in his walk around...

Страница 12: ...ts 3 Measure the input voltage between the 24 and GND posts of the equalizer This voltage should be between 25 5 volts and 29 0 volts If it isn t then check the alternator and 24 volt voltage regulato...

Страница 13: ...e the DC connection sequence is not an issue Family 3 4 and 5 Equalizers will not function properly unless all three battery connections are made Battery A and Battery B voltages both must be above 8...

Страница 14: ...ance If Battery A voltage falls below approximately 8 volts the equalizer will shut itself OFF To correct the overload condition the 12 volt load must be reduced or the equalizer capacity must be incr...

Страница 15: ...o other warranties that extend beyond those described on the face of this warranty Some states do not allow limitation on how long an implied warranty lasts so the above limitations may not apply to y...

Страница 16: ...TTERY EQUALIZER OWNER S MANUAL 16 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com...

Отзывы: