Vanner VoltMaster  60-100 Скачать руководство пользователя страница 11

 !"#$%$%&'(

 !"#$%$%&'(

 Incorporated

                               

Testing and Trouble Shooting

BATTERY EQUALIZER                                                                     OWNER’S MANUAL

11

A)

No, the Battery Equalizer electronically limits the output current to a value less  than  the  amount
required to trip the circuit breaker.  (Extreme conditions, such as 28 VDC input with 8 VDC output
at very high ambient temperatures, may cause the circuit breaker to trip.)

Q)

Why is the Battery Equalizer' s  circuit  breaker value lower  than  its  output  current  rating  (35  amp
circuit breaker in model 60-50A)?

A)

The circuit breaker is in the ground circuit.  Due to the equalizer’s two to one (24/12 VDC) voltage
conversion,  the  model  60-50A  requires  25  amps  at  24VDC  input  to  produce  about  50  amps
output at 12 VDC.  Therefore, a 35 amp circuit breaker in the GND circuit will properly protect for
the maximum 25 amp rating.

Q)

What causes the circuit breaker to trip on a Battery Equalizer?

A1)

The Battery Equalizer' s circuit breaker is designed to trip when the +12 volt to 

GND terminals are

exposed to reverse polarity.

A2)

With the Battery Equalizer' s 

GND terminal connected to chassis and the battery negative terminal

disconnected, a short between a +24 volt circuit and chassis will pull the chassis up to +24 volts,
causing a reverse polarity on the +12 volt to GND circuits.  The circuit breaker trips to protect the
Battery Equalizer.

A3)

With the  Battery  Equalizer' s GND  terminal  connected to  chassis  and  the  battery  negative  cable
disconnected,  24  volt  loads  (e.g.,  starter  motor)  will  pull  the  chassis  up  to  +24  volt  causing  a
reverse polarity on the Battery Equalizer' s +12 Volt to 

GND circuits.  The circuit breaker will trip to

protect the Battery Equalizer.

A4)

Since the above reverse polarity conditions may occur during bus maintenance it is
recommended that the service personnel verify the circuit breaker is IN before releasing the bus
for service and the tour bus operator do the same in his “walk around”.

Q)

What are some known conditions that could cause Battery Equalizer problems?

A1)

Corrosive  liquids  or  water  forced  into  the  Battery  Equalizer' s  case  from  high  pressure  spray
cleaning could shorten the normal life expectancy.

A2)

Drilling  into  the  case  (except  for  the  mounting  flanges)  can  shorten  the  life  or  prevent  the  unit
from  operating.    The  installer  may  not  realize  the  Battery  Equalizer  is  not  operating  correctly
unless  a  12  volt  load  is  applied  to  the  system  and  the  Battery  Equalizer  12  volt  current  is
measured.

A3)

Too  small  of  wire  or  bad  connections  will  allow  the  Battery  balance  to  be  less  than  optimum.
Voltage  loss  in  wire  from  the  battery' s  +24  volt  terminal  to  the  Battery  Equalizer' s  +24  volt
terminal  should  be  0.05  VDC  maximum;  from  the  battery' s  +12  volt  terminal  to  the  Battery
Equalizer' s +12 volt terminal should be 0.10 

VDC maximum, and from the battery ground terminal

to the Battery Equalizer' s 

GND terminal should be 0.05 VDC maximum, when the +12 volt load is

causing the Battery Equalizer to operate at 100% capacity.

A4)

Installing the Battery Equalizer in a location where it will be exposed to battery fumes will shorten
its normal life.  Acid fumes are heavier than air.  Installation of Battery Equalizers on the battery
mounting  surface  near  the  bottom  of the  batteries  have  caused  severe  corrosion  to  the  Battery
Equalizers.    However,  installation  of  Battery  Equalizers  3  or  more  inches  above  the  top  of  the
batteries have not caused problems.

Q)

Can different models of equalizers be paralleled?

A)

Yes, any combination of models from Family 1, Family 3 and Family 4 may be paralleled. Family
2 models may only be paralleled with other Family 2 models.

Содержание VoltMaster 60-100

Страница 1: ...ly 4 Family 5 60 10B 60 100C 60 60 65 60 66 60 60 20A 60 100D 60 60M 65 60M 66 80 60 50A 60 100E 60 80 65 80 66 100 60 50E 60 100 65 100 60 50M Table of Contents Introduction 2 Specifications 3 Theory...

Страница 2: ...tery Equalizer connects to the 24 volt 12 volt and ground terminals of the battery system When the 12 volt loads require power the Battery Equalizer ensures that the current is taken equally from both...

Страница 3: ...unting Location Mount on a flat surface close to the batteries to allow short cable runs Vertical mounting with terminals down is recommended Location should be protected from battery acid and gases 2...

Страница 4: ...the voltage balance and therefore the charge acceptance rate of each battery Family 3 and Family 4 Equalizers hold Battery A and B voltages to within 0 05 volts under light loads and to within 0 1 vo...

Страница 5: ...ng small adjustments to keep the batteries in balance Scenario 2 Both 24 volt and 12 volt loads present alternator is OFF The Battery Equalizer will insure that both batteries will discharge at the sa...

Страница 6: ...CH 24V ALT _ 24V VANNER Battery Equalizer 12V GND 12V Battery B 12V Battery A 12V 12 Volt Loads VANNER DC to AC Inverter 120VAC To AC Loads 24 Volt Loads 24V F2 F1 MARINE ENGINE BATTERY SYSTEM HOUSE B...

Страница 7: ...aining batteries or flammable materials Safety goggles should always be worn when working near batteries Mounting Location The Equalizer may be mounted in any orientation however the recommended orien...

Страница 8: ...ttery Disconnect Switch 24V VANNER Battery Equalizer 12V GND 12V Battery B 12V Battery A 12V 12 Volt Loads Radio 24 Volt Loads 24V 24V ALT _ HIGH CURRENT DIODE BATTERY DISCONNECT SWITCH F2 F1 The syst...

Страница 9: ...7 13 1 10 9 8 2 6 5 3 3 1 0 191930333 82 9 41 4 16 6 13 8 10 4 8 3 4 1 2 0 191930346 105 5 52 7 21 1 17 6 13 2 10 5 5 3 Fuse F1 20 amp 30 amp 80 amp 80 amp 100 amp 125 amp 250 amp Fuse F2 10 amp 15 a...

Страница 10: ...same 12 volt lamp between the 12 and GND terminals of the Equalizer The lamp should light and stay lit If the lamp does not light the light then goes out or the light dims the Equalizer requires repa...

Страница 11: ...occur during bus maintenance it is recommended that the service personnel verify the circuit breaker is IN before releasing the bus for service and the tour bus operator do the same in his walk around...

Страница 12: ...ts 3 Measure the input voltage between the 24 and GND posts of the equalizer This voltage should be between 25 5 volts and 29 0 volts If it isn t then check the alternator and 24 volt voltage regulato...

Страница 13: ...e the DC connection sequence is not an issue Family 3 4 and 5 Equalizers will not function properly unless all three battery connections are made Battery A and Battery B voltages both must be above 8...

Страница 14: ...ance If Battery A voltage falls below approximately 8 volts the equalizer will shut itself OFF To correct the overload condition the 12 volt load must be reduced or the equalizer capacity must be incr...

Страница 15: ...o other warranties that extend beyond those described on the face of this warranty Some states do not allow limitation on how long an implied warranty lasts so the above limitations may not apply to y...

Страница 16: ...TTERY EQUALIZER OWNER S MANUAL 16 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com...

Отзывы: