5. INSTALLATION and START UP

Unpacking the Inverter

1. Inspect the shipping container and equipment for loose or damaged parts. If any damage is found,
immediately notify the freight carrier.

Inverter Installation Considerations

1. Mounting: Locate a secure, dry, flat horizontal or vertical surface large enough to mount the inverter.

The location should be as close to the battery as possible, usually within six feet, but not in the same
compartment and should provide adequate ventilation while the inverter is operating. The location
must be clean, dry and free from road spray, dripping water or other moisture contamination.

2. Cooling Fan Clearance: The mounting location must allow unobstructed airflow for cooling. Allow a

minimum clearance of 1½ inches (40 mm) on the left, right and back sides of the inverter. The Cooling
Fan is a thermostatically controlled intake fan. Air is drawn into the inverter from the front and side
vents and exhausted through the fans. Obstruction of the fan intake or the exhaust vents will diminish
the inverter output capacity due to overheating.

DC Wiring Considerations

1.

A DC FUSE IS REQUIRED

 to properly protect the inverter in case the battery cables are connected

backward (reverse polarity).

2.

The wiring of your inverter installation should conform to the National Electric Code (NEC) and any
other state or local codes in effect at the time of installation. These codes have been written for your
protection and their requirements should be followed. Article 551 of the NEC requires any DC cable
from a battery, which measures longer than 18 inches along its length, be protected by a fuse.

3.

BE AWARE

, as a large number of capacitors become charged upon completion of the DC circuit,

THERE WILL BE A LARGE SPARK

 when the last battery connection is made. The spark is normal

and will occur every time the batteries are connected. It is advisable to make the last DC connection
at the input fuse, not at the battery, to reduce the risk of battery explosion.

4.

Route the AC output wiring and DC power wiring with as much physical separation as possible from
low voltage wiring such as audio and video signal wires.

5.

Route the DC positive and negative cables as close together as possible and use cable ties to keep
them together. This reduces electromagnetic radiation that could interfere with sensitive electronics.

6.

If passing through steel or other ferrous metal walls, the DC input cables need to pass through the
same hole to prevent causing a transformer effect. If two holes are required, cut a slot to connect the
two holes to prevent heating of the ferrous metal.

Содержание VLT12-600

Страница 1: ...rter VLT12 600 VLT12 1000 VLT12 1500 VLT24 600 VLT24 1000 VLT24 1500 VLT48 1000 VLT48 1500 Owner s Manual D910106 Rev B Rev May 24 2007 60Hz Models VLTE12 600 VLTE12 1000 VLTE12 1500 VLTE24 600 VLTE24...

Страница 2: ...ies True Sine Wave Inverter Owner s Manual 2 Vanner Incorporated 4282 Reynolds Drive Hilliard OH 43026 800 AC POWER 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail sales vanner co...

Страница 3: ...cator 11 Overload Indicator 11 ON OFF Switch 11 Inverter Indicator Light 11 GFCI Duplex Receptacle 11 Section 5 Installation and Setup 12 Unpacking the Inverter 12 Inverter Installation Considerations...

Страница 4: ...liarize yourself with the model numbers of the inverter and optional accessories you have purchased before proceeding with this manual If you require additional information please contact your dealer...

Страница 5: ...attery Shutdown Over Temperature Shutdown Overload Inverter ON OFF Indicator Overload Short Circuit Reverse Polarity fuse Over Under Input Voltage OverTemp Inverter may be mounted in any orientation M...

Страница 6: ...ed cooling intake fan Definitions Load Demand Feature and Load Demand Mode The Load Demand Feature is an energy conserving feature which allows the inverter to enter the Load Demand Mode whenever the...

Страница 7: ...nt fire or explosion DO NOT install in confined areas or compartments that contain batteries or flam mable materials WARNING Improper use of this product may result in risk of electrical shock Both AC...

Страница 8: ...ries or flammable materials or in locations that require ignition protected equipment This includes any space containing gasoline powered machinery fuel tanks or joints fittings or other connections b...

Страница 9: ...Rear entry for negative DC input cable 2 Rear entry for positive DC input cable 3 Rear entry for Remote Control RS 232 Connection 4 Chassis Ground Bonding Lug 5 Cooling Fans Draw air in through intake...

Страница 10: ...light is in the red areas of the graph the inverter may shut itself OFF 7 Load Watt Indicator The AC load watt bar graph indicates the power drawn from the inverter It will indicate wattage by loads...

Страница 11: ...F switch to the OFF position correct the fault condition and turn the inverter back ON 12 ON OFF Switch and RESET Switch The ON OFF Switch is a two position rocker switch used to turn the inverter ON...

Страница 12: ...se the battery cables are connected backward reverse polarity 2 The wiring of your inverter installation should conform to the National Electric Code NEC and any other state or local codes in effect a...

Страница 13: ...location should be within 18 of the battery and accessible for visual inspection and replacement If possible locate so the last DC connection can safely be made at the fuse 4 Prepare DC cable ends 5...

Страница 14: ...sufficient ventilation DC cables have been connected to the inverter but not yet to the battery AC wiring has been completed and all remote connections have been checked the Start up and Testing proce...

Страница 15: ...ble Shooting Procedures The following are the most common questions heard by Vanner service professionals If your situation does not apply to the following categories please contact your local Vanner...

Страница 16: ...ove obstructions from air exhaust vents and cooling fan Problem Overload Indicator Light is ON when AC load is applied Check Verify AC load is within the inverter s rated capacity Remove excessive loa...

Страница 17: ...CI Test Record For maximum protection against electrical shock hazard operate the Test Switch on the Ground Fault Circuit Interrupter at least once a month and record the values in this supplied table...

Страница 18: ...nverter Owner s Manual 18 Vanner Incorporated 4282 Reynolds Drive Hilliard OH 43026 800 AC POWER 800 227 6937 T e l 614 771 2718 Fax 614 771 4904 www vanner com e mail sales vanner com Copyright 2007...

Отзывы: