Vanguard VMH26TPB Скачать руководство пользователя страница 6

111043-01B

For more information, visit www.desatech.com

For more information, visit www.desatech.com

6

AIR FOR COMBUSTION AND
VENTILATION

Continued

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1.3/ NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m

3

 per kw) of the aggregate input rating

of all appliances installed in that space and an unconfined space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m

3

 per kw) of the aggregate input rating of all appliances

installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.

* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m

3

 per kw) of the aggregate input rating

of all appliances installed in that space and an unconfined space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m

3

 per kw) of the aggregate input rating of all appliances

installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.

* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION

Determining if You Have a Confined or
Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining

rooms with doorless passageways or ventilation grills between the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = ___________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling

height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.

2.

Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example:

 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum

Btu/Hr the space can support)

 WARNING: If the area in which the heater may be

operated is smaller than that defined as an uncon-
fined space or if the building is of unusually tight
construction, provide adequate combustion and ven-
tilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec-
tion 5.3 or applicable local codes.

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances*  + _____________ Btu/Hr

Total                             = _____________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws com-
bustion air from the outdoors and vents to the outdoors.

Example:

Gas water heater

_____________ Btu/Hr

Vent-free heater

+ _____________ Btu/Hr

Total

= _____________ Btu/Hr

4.

Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

56,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:

A.

Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See Ventilation Air From
Inside Building
, page 7.

B.

Vent room directly to the outdoors. See Ventilation Air From Out-
doors
, page 7.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room
unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.

30,000

26,000

56,000

AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation (Cont.)
Determining Fresh-Air Flow for Heater Location

Содержание VMH26TPB

Страница 1: ...for correct installa tion and operational procedures For as sistance or additional information con sult a qualified installer service agency or the gas supplier This appliance may be installed in an a...

Страница 2: ...ng fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting Due to high temperatures the appliance should be located out of traffic and away from furniture and...

Страница 3: ...n adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This fireplace has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the fireplace if...

Страница 4: ...nsing ODS safetyshutoffsystem TheODS pilotisarequiredfeatureforvent free room fireplaces The ODS pilot shuts off the fireplace if there is not enough fresh air PIEZO IGNITION SYSTEM This fireplace has...

Страница 5: ...fresh air for combustion and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is defined as construction where a wall...

Страница 6: ...soropen ings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support __________ volume of space x 20 Maxi...

Страница 7: ...e National Fuel Gas Code ANSI Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts IMPORTANT Do not provide openings for inlet or outlet air i...

Страница 8: ...unting Clearances As Viewed From Front of Fireplace Shown Built In the Wall INSTALLATION Continued IMPORTANT Vent free fireplaces add moisture to the air Although this is beneficial installing firepla...

Страница 9: ...ning to use blower locate fireplace near an electrical outlet 267 8 267 8 3 4 Off The Floor Minimum 10 1 2 Figure 9 Rough Opening for Installing in Wall WARNING If pre wiring do not connect wiring to...

Страница 10: ...replace and set aside 2 Place fireplace on wood base 3 Place mantel around fireplace base assembly 4 Assemble brass trim kit See Assembling Brass Trim page 11 13 16 19 21 2 1 2 6 8 10 Note All vertica...

Страница 11: ...s louvers 1 3 4 Screw Wood Base INSTALLATION Continued Shoulder Screws Assembled Brass Trim Hole for 3 wood screw for attaching fireplace to mantel Hole for 3 wood screw for attaching fireplace to woo...

Страница 12: ...the assembly down see Figure 17 2 Using short Phillips screwdriver remove the screw under the center of the branch support Rotate valve cover shield clock wise and slide out IMPORTANT Do not remove sh...

Страница 13: ...valve cover shield The other hole is for a strain relief clamp not supplied to secure incoming electrical supply 2 Follow steps 2 through 6 in Installing BlowerAssembly page 12 Also remove black wire...

Страница 14: ...onry drill at least 1 deep 2 Fold floor anchor as shown in Figure 22 3 Insert floor anchor wings first into hole Tap anchor flush to floor 4 Insert mounting screws through base and into floor anchors...

Страница 15: ...e Figure 25 Carefully lift up branch support and remove from fireplace see Figure 25 3 Route flexible gas line included from fireplace control to equip mentshutoffvalvethroughsideorrearaccessholesinou...

Страница 16: ...leak detection fluid to gas joints Bubbles form ing show a leak 4 Correct all leaks at once Pressure Testing Fireplace Gas Connections 1 Open equipment shutoff valve see Figure 27 2 Open main gas valv...

Страница 17: ...ire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service techni cian or...

Страница 18: ...ING PROCEDURE OPERATING FIREPLACE Continued OPERATING BLOWER OFF ON Auto Off On Switch This blower has three settings ON OFF and AUTO In the ON position the blower will operate constantly In the OFF p...

Страница 19: ...with a mild soap and water mixture Wipe the cabinet to remove dust INSPECTING BURNER Burner Flame Pattern CLEANING AND MAINTENANCE Cleaning Burner Injector Holder and Pilot Air Inlet Hole Cabinet WAR...

Страница 20: ...mocouple damaged 8 Control valve damaged REMEDY 1 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 2 Reconnect ignitor cable 3 Replace ignitor cable 4 Replace piezo ignitor...

Страница 21: ...rough 10 4 Clean burner see Cleaning and Mainte nance page 19 or replace burner orifice 1 Turn heater off when using furniture polish wax carpet cleaners or similar products OBSERVED PROBLEM Burner do...

Страница 22: ...1 Gas leak SeeWarning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and burner 2 Gas leak SeeWarning statement at top of page 1 Not enough combustion ventil...

Страница 23: ...DESA Heating Products Techni cal Service Department at 1 866 672 6040 for referral information When calling DESA Heating Products have ready your name your address model and serial numbers of your fi...

Страница 24: ...satech com 24 ILLUSTRATED PARTS BREAKDOWN MODELS VMH26TPB Shown AND VMH26TNB 12 23 29 40 32 36 38 13 7 8 33 40 11 10 4 7 30 1 3 2 9 17 19 6 22 31 21 41 42 16 15 18 24 28 34 25 27 20 4 35 12 24 12 1 14...

Страница 25: ...se 1 20 102649 01CK 102649 01CK Branch Support 1 21 099415 09 099415 10 Gas Regulator 1 22 102875 01 102875 01 Regulator Bracket 1 23 101381 01 101381 01 Valve Cover and Piezo 1 24 099387 11 099387 11...

Страница 26: ...Equipment shutoff valve with 1 8 NPT tap THERMOSTATICALLY CONTROLLED BLOWER KIT GA3450T Provides better heat distribution Makes fireplace more efficient Automatically turns off and on as needed BRASS...

Страница 27: ...ed College Completed Graduate School 13 Age of Purchaser Under 20 20 29 30 39 40 49 50 59 60 or Over 14 Buyer s total annual household income Under 15 000 15 000 to 19 999 20 000 to 34 999 35 000 to 4...

Страница 28: ...111043 01B For more information visit www desatech com For more information visit www desatech com 28 2701 Industrial Drive P O Box 90004 Bowling Green KY 42102 9004 Postage Required TAPE TAPE...

Страница 29: ...________________________________________________________ _______________________________________________________________________________________________ _______________________________________________...

Страница 30: ...as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost labor transportation and any and all such other costs related to repairing...

Отзывы: