Van Air Systems AC-65 Скачать руководство пользователя страница 6

PAGE 6

4.1 START UP

Pressurize the compressed air system.  If the aftercooler was 

interlocked with the compressor, the aftercooler will begin to 

operate immediately.  If the aftercooler was wired on a separate 

electrical source, turn on the source.

Open the inlet and outlet isolation valves on the aftercooler (if 

installed).  Close the bypass valve.  The aftercooler is ready for 

operation.

4.2 OPERATION

The operation of the aftercooler is simple.  The fan rotates, 

moving ambient air across the core.  The ambient air flow cools 

the compressed air inside the core.  The aftercooler will 

automatically operate as long as electrical power is supplied to 

the unit.

OPERATION 

SECTION 4

MAINTENANCE 

SECTION 5

5.0 MAINTENANCE INSTRUCTIONS

 

WARNING

BEFORE STARTING INSTALLATION OR MAINTENANCE 

PROCEDURES, TURN OFF ELECTRICAL POWER AND 

COMPLETELY DEPRESSURIZE THE UNIT.  FAILURE TO 

HEED THIS WARNING MAY RESULT IN SERIOUS PER-

SONAL INJURY AND/OR DAMAGE TO THE UNIT.

DO NOT REMOVE, REPAIR, OR REPLACE ANY ITEM ON 

THIS UNIT WHILE IT IS PRESSURIZED.

DO NOT REMOVE THE FAN GUARD WHILE THE AFTER-

COOLER IS OPERATING.  PERSONAL CONTACT WITH 

THE ROTATING FAN BLADE MAY RESULT IN SERIOUS 

PERSONAL INJURY.

Inspect the aftercooler regularly for loose bolts and connec

-

tions, rust and corrosion, and dirty or clogged heat transfer 

surfaces.

SCHEDULED MAINTENANCE

MONTHLY

- Clean exterior of the aftercooler core

SEMI ANUALLY

- Grease motors that have alemite fittings.  Apply 1 to 2 full 

strokes with a grease gun.

YEARLY

- Clean the interior of the aftercooler core

5.1 CORE EXTERIOR CLEANING 

The outside of the core should be cleaned regularly.   Accumu

-

lation of dirt and other contaminants such as oils will greatly 

reduce the efficiency of the aftercooler.

Normal accumulation of dirt can be removed by blowing the 

core off with compressed air.  If the core becomes contaminated 

with oil-laden particles, the motor should be removed and the 

core can be cleaned with a non-flammable degreaser.  Follow 

with hot water rinse and dry thoroughly.  The core can also be 

steam cleaned.  

Use extreme care when cleaning the core, 

as the aluminum fins can be easily damaged.  DO NOT USE 

CAUSTIC CLEANERS.

CAUTION

NEVER USE SOLVENTS CONTAINING STRONG ACID 

OR ALKALINE BASES TO CLEAN THE CORE.  DAM-

AGE TO THE CORE MAY OCCUR.

4.3 SHUT DOWN

To shut down the aftercooler, turn off the electrical power 

source.  If the aftercooler was interlocked with the compressor, 

the aftercooler will automatically turn off with the compressor.

Open the bypass valve and close the inlet and outlet isolation 

valves (if installed).

Manually override the automatic drain on the separator to com

-

pletely depressurize the aftercooler.

5.2 CORE INTERIOR CLEANING 

The inside of the core should be cleaned once a year to return 

the unit to full capacity.  Excess lubricating fluids can build up 

on the inside of the core and greatly reduce the efficiency of the 

aftercooler.

Shut down the aftercooler per Section 4.3 and completely 

depresusrize the unit.  Disconnect the aftercooler from the air 

system.

The interior of the core can be cleaned by circulating a mild 

cleaning solution through the core to remove the deposits.  In 

most cases, a mild alkaline solution such as OAKITE or equal 

is satisfactory.  For extreme conditions, it may be necessary to 

use a weak solution of INHIBITED hydrochloric acid.  Circulate 

the solution through the core until it is clean.  Once the core 

is clean, thoroughly rinse the core to remove all traces of the 

cleaning solution before re-connecting to the air system.  Always 

follow the instructions supplied with the cleaning agent.

All filters and separators should also be cleaned and serviced 

after the inside of the afercooler has been cleaned.

5.3 STORAGE

Store the aftercooler in a dry location that maintains a constant 

temperature.  The aftercooler shouold not be moved from a 

warm area to a cold area in order to minimize condensation 

inside the core.

For storage up to 6 months, drain the cooler and seal the open

-

ings.

For storage from 6 months to 24 months, flush the cooler with 

oil and seal the openings.  Remove all protection oil from the 

aftercooler before connecting it to air system for operation.

For storage longer than 24 months, completely fill the cooler 

with oil and seal the openings.  The cooler should be flushed, 

inspected, refilled with oil and sealed every 24 months during 

storage. Drain the aftercooler and remove all protection oil from 

the aftercooler before connecting it to air system for operation.

Содержание AC-65

Страница 1: ...OVE THE RATED OPERATING CONDITIONS OPERATION ABOVE SPECIFIED CONDITIONS WILL RESULT IN DECREASED PERFORMANCE POSSIBLE DAMAGE TO THE UNIT AND OR PERSONAL INJURY NEVER OPERATE THIS AFTERCOOLER IF THERE...

Страница 2: ...C 105 AC 125 15 87 158 296 10 61 112 216 5 29 56 109 20 101 180 337 5 26 51 97 10 56 105 204 15 69 126 241 20 82 149 280 5 24 47 90 10 45 85 166 15 62 116 223 20 74 138 265 5 21 40 77 10 37 71 138 15...

Страница 3: ...THE AFTERCOOLER FROM VIBRATION IN THE PIPING REFERENCE Section 3 3 for instructions The location should be level and capable of supporting the aftercooler and all components and piping to be installed...

Страница 4: ...N IN THE PIPING WILL CAUSE DAMAGE TO THE AFTERCOOLER CORE TO ENSURE PROPER OPERATION MAKE SURE THAT THE INLET AND OUTLET PIPING ARE CORRECTLY CONNECTED TO THE UNIT REFERENCE FIGURE 2 2 If the aftercoo...

Страница 5: ...AL CODES IF THE AFTERCOOLER IS TO BE INSTALLED OUT DOORS OR IN AN EXTREMELY HUMID ATMOSPHERE MAKE SURE THAT ALL WIRING AND COMPONENTS ARE PROPERLY RATED VERIFY THAT THE POWER SOURCE MATCHES THE AF TER...

Страница 6: ...STIC CLEANERS CAUTION NEVER USE SOLVENTS CONTAINING STRONG ACID OR ALKALINE BASES TO CLEAN THE CORE DAM AGE TO THE CORE MAY OCCUR 4 3 SHUT DOWN To shut down the aftercooler turn off the electrical pow...

Страница 7: ...em 1 Dirty core or restricted air flow Inspect the core for deposits of dirt and or oils If the core is contaminated clean it as outlined in Sections 5 1 and 5 2 Check for obstructions around the afte...

Страница 8: ...ERs DANGER ELECTRICAL SHOCK FROM IMPROPER GROUNDING CAN CAUSE INJURY OR DEATH GROUND UNIT AND RELATED EQUIPMENT ACCORDING TO NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS WARNING WARNING READ THE OPE...