Van Air Systems AC-65 Скачать руководство пользователя страница 5

PAGE 5   

INSTALLATION 

SECTION 4

FIGURE 3C SEPARATOR

D

1" NPT
1-1/2" NPT

E

1/8" NPT
1/4" NPT

MWP

(PSIG)

200
200

MAX

120
400

MIN

11

60 

FLOW 

(SCFM)

A

10.00"
17.00"

B

3.35"
6.70"

C

0.98"
2.00"

MODEL

S-10-AD
S-30-M

SEPARATOR

S-10-AD
S-30-M

AFTERCOOER

AC-65
AC-105 & AC-125

PART NO.

83-0751
83-0751

DRAIN

FD-1
FD-1

PART NO.

83-0744
83-0746

3.5  FREEZE PROTECTION 

If the aftercooler is to be installed in a location where ambient 

temperatures may fall below 38

o

F, heat tracing and/or insulation 

must be used on the outlet piping to the separator, the separa

-

tor, and the drain piping.  The aftercooler must be protected 

from the direct wind, i.e. a roof and/or walls.

The aftercooler should be turned off when ambient temperatures 

fall below 38

o

F.

3.6 SEPARATOR INSTALLATION

 

CAUTION

IF THE SEPARATOR DRAIN IS TO BE CONNECTED INTO 

A REMOTE OR COMMON DRAIN LINE, MAKE SURE 

THAT IT IS VENTED.

THE DISCHARGE FROM THE SEPARATOR MAY CON-

TAIN COMPRESSOR LUBRICANTS.  COMPLY WITH ALL 

REGULATIONS CONCERNING DISPOSAL OF SUCH 

FLUIDS.

When the process air is cooled by the aftercooler, moisture 

condenses and accumulates in the outlet of the aftercooler.  

To efficiently remove this liquid from the air system, a 

separator with a FD-1 float drain must be installed immediately 

downstream of the aftercooler.  

Install the separator as outlined in the Installation, Operation, 

and Maintenance Instructions supplied with the component.  If 

a separator was not ordered with the aftercooler, one can be 

ordered from your VAN AIR distributor. 

3.7 ELECTRICAL CONNECTIONS

 

CAUTION

TURN OFF MAIN POWER SUPPLY BEFORE WIRING TO 

THE AFTERCOOLER.

MAKE SURE THAT ALL USER SUPPLIED WIRING 

IS PROPERLY SIZED TO HANDLE THE AMPERAGE 

REQUIRED BY THE AFTERCOOLER AND ANY AD-

DITIONAL EQUIPMENT.  ALWAYS COMPLY WITH THE 

NATIONAL ELECTRICAL CODE AND ALL APPLICABLE 

FEDERAL, STATE AND LOCAL CODES.

IF THE AFTERCOOLER IS TO BE INSTALLED OUT-

DOORS OR IN AN EXTREMELY HUMID ATMOSPHERE, 

MAKE SURE THAT ALL WIRING AND COMPONENTS 

ARE PROPERLY RATED.

VERIFY THAT THE POWER SOURCE MATCHES THE AF-

TERCOOLER ELECTRICAL REQUIREMENTS BEFORE 

MAKING ANY CONNECTIONS.  REFERENCE MOTOR 

DATA TAG FOR INFORMATION.

TO PREVENT POSSIBLE ELECTRICAL SHOCK, IT IS IM-

PORTANT THAT THIS UNIT IS PROPERLY GROUNDED.

The aftercooler electrical requirements are listed on the 

equipment data tag and in Figure 2.  If there are any 

discrepancies between the data tag and Figure 2, use the 

information on the tag. 

Remove the cover from the electrical junction box on the after

-

cooler motor.  Using the wiring diagram on the motor as refer

-

ence, make the necessary wiring connections.  Several ways 

to wire the unit are listed below.  Make the connections for the 

pertinent application(s).

1.  DEDICATED POWER SUPPLY AND DISCONNECT

Install a properly sized fused disconnect before the 

aftercooler.  Make the necessary wire connections and re-

install the junction box cover.

2.  INTERLOCKED WITH COMPRESSOR MOTOR STARTER

The aftercooler can be interlocked with the air compressor 

starter.  This allows the aftercooler to operate only when the 

air compressor is operating.

If a set of auxiliary, normally open contacts is available on the 

air compressor magnetic starter, make necessary wiring con

-

nections from the contacts to the aftercooler.

If a set of auxiliary contacts is not available, use a properly 

sized contactor.  Wire the contactor's holding coil in parallel 

with the air compressor starter holding coil.  Make the neces

-

sary wiring connections from the contactor to the aftercooler.

3.7-1 FAN MOTOR ROTATION

The rotation of the fan motor(s) is important. Units with 3 

phase power should be checked for proper rotation after 

installation.

Energize the unit. Observe the rotation and air flow direction. 

referece Section 2.2 for air flow direction. If the air does not 

flow in the proper direction, turn off the unit and switch two of 

the main power legs.

Содержание AC-65

Страница 1: ...OVE THE RATED OPERATING CONDITIONS OPERATION ABOVE SPECIFIED CONDITIONS WILL RESULT IN DECREASED PERFORMANCE POSSIBLE DAMAGE TO THE UNIT AND OR PERSONAL INJURY NEVER OPERATE THIS AFTERCOOLER IF THERE...

Страница 2: ...C 105 AC 125 15 87 158 296 10 61 112 216 5 29 56 109 20 101 180 337 5 26 51 97 10 56 105 204 15 69 126 241 20 82 149 280 5 24 47 90 10 45 85 166 15 62 116 223 20 74 138 265 5 21 40 77 10 37 71 138 15...

Страница 3: ...THE AFTERCOOLER FROM VIBRATION IN THE PIPING REFERENCE Section 3 3 for instructions The location should be level and capable of supporting the aftercooler and all components and piping to be installed...

Страница 4: ...N IN THE PIPING WILL CAUSE DAMAGE TO THE AFTERCOOLER CORE TO ENSURE PROPER OPERATION MAKE SURE THAT THE INLET AND OUTLET PIPING ARE CORRECTLY CONNECTED TO THE UNIT REFERENCE FIGURE 2 2 If the aftercoo...

Страница 5: ...AL CODES IF THE AFTERCOOLER IS TO BE INSTALLED OUT DOORS OR IN AN EXTREMELY HUMID ATMOSPHERE MAKE SURE THAT ALL WIRING AND COMPONENTS ARE PROPERLY RATED VERIFY THAT THE POWER SOURCE MATCHES THE AF TER...

Страница 6: ...STIC CLEANERS CAUTION NEVER USE SOLVENTS CONTAINING STRONG ACID OR ALKALINE BASES TO CLEAN THE CORE DAM AGE TO THE CORE MAY OCCUR 4 3 SHUT DOWN To shut down the aftercooler turn off the electrical pow...

Страница 7: ...em 1 Dirty core or restricted air flow Inspect the core for deposits of dirt and or oils If the core is contaminated clean it as outlined in Sections 5 1 and 5 2 Check for obstructions around the afte...

Страница 8: ...ERs DANGER ELECTRICAL SHOCK FROM IMPROPER GROUNDING CAN CAUSE INJURY OR DEATH GROUND UNIT AND RELATED EQUIPMENT ACCORDING TO NATIONAL ELECTRICAL CODE AND LOCAL REGULATIONS WARNING WARNING READ THE OPE...

Отзывы: