VAMP Ltd
Feeder and motor manager
Operation and configuration
VAMP 257
VM257.EN002
VAMP 24h support phone +358 (0)20 753 3264
19
3.4.1.
Opening operating levels
1.
Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 3.4.1-1. Opening the operating level
2.
Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3.
Push the ENTER key.
3.4.2.
Password handling
The passwords can only be changed using VAMPSET software
connected to the local RS-232 port on the manager.
It is possible to restore the password(s) in case the password is
lost or forgotten. In order to restore the password(s), a manager
program is needed. The serial port settings are 38400 bps, 8
data bits, no parity and one stop bit. The bit rate is
configurable via the front panel.
Command Description
get pwd_break
Get the break code (Example:
6569403)
get serno
Get the serial number of the
manager (Example: 12345)
Send both numbers to [email protected]. A device specific
break code is sent back to you. The break code will be valid for
the next two weeks.
Command Description
set pwd_break=4435876
Break the passwords (The
number “4435876” is sent by
VAMP Ltd.)
Now the passwords are restored to the default values (See
chapter 3.4).