INSTALLATION AND MAINTENANCE INSTRUCTIONS 

FLOAT AND THERMOSTATIC STEAM TRAPS 

FLT14I 

 
 

GENERAL 
 

 

These  instructions  must  be  carefully  read  before  any  work  involving  products  supplied  by  VALSTEAM  ADCA 
ENGINEERING S.A. is undertaken. 

 

 

The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage 
to the trap or equipment. 

 

 

They  give  their  maximum  performance  only  when  the  equipment  associated  with  them  is  correctly  sized  and 
installed in accordance with our recommendations. 

 
 
Note: 
 

 

Current  regional  safety  regulations  should  be  take  in  to  account  and  followed,  while  doing  the  installation  and 
maintenance work. 

 

Handling, installation and maintenance work must be carried out by trained personnel. A supervisor must follow 
and check all activities. 

 

For the problems that cannot be solve with the help of this instructions, please contact the supplier or the 
manufacturer. 

 

The manufacturer reserves the right to change the design and material of this product without notice. 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
CE  Marking:  
This  product  has  been  designed  for  use  on  steam  and  water  which  are  in  Group  2  of  the  PED-
European  Pressure  Equipment  Directive  97/23/EC  and  it  comply  with  those  requirements.  The  product  fall  within 
category SEP and must not be CE marked. 

 
 
 
 
 
 
 

MODEL

Max. Differential pressure

FLT14I - 4,5

4,5 bar

FLT14I - 10

10 bar

FLT14I - 14

14 bar

PMO - Max. operating pressure          14  bar
TMO - Max. operating temperature    198 ºC
* According to EN1092-1:2007 ;  ** Acc. to EN1759-1:2004

 BODY LIMITING CONDITIONS    

250 ºC

 FLANGED                      

PN16* 

 FLANGED                                 

ANSI 150  ** 

RELATED              

TEMP.

150 ºC

13,4 bar

200 ºC

100 ºC

ALLOW. PRES.

Body limiting conditions PN16 or below, depending on the type 
of connection adopted. Rating PN16 for thread.

ALLOW. PRES.

16 bar

12 bar

16 bar

13,6 bar

14,8 bar

12,7 bar

14,5 bar

Содержание FLT14I Series

Страница 1: ...t be carried out by trained personnel A supervisor must follow and check all activities For the problems that cannot be solve with the help of this instructions please contact the supplier or the manu...

Страница 2: ...advised to assess the risks taking into account the task the individual the load and the working environment Before starting work ensure that you have suitable tools and or consumables available Use...

Страница 3: ...p maintenance The by pass must be kept close during the normal operation Procedure Prior to install check that the product is suitable for the intended application materials and pressure temperature r...

Страница 4: ...up it is recommended to check pipe connections for leaks and retighten the connections if necessary MAINTENANCE We recommend the steam traps to be serviced as necessary Steam traps should be checked...

Страница 5: ...reason of contamination Check the steam trap D P and substitute Replace the steam trap by a superior DN or use ADCAMAT Replace Temporary condensate accumulation Steam blocking Downsizing Use a steam...

Страница 6: ...ARTS Available spare parts POS Nr DESIGNATION M ATERIAL 1 Body CF8M 1 4408 2 Cover CF8M 1 4408 3 Gasket Stainless st Graphite 4 Seat AISI 410 1 4006 5 Valve AISI 440C 1 4125 6 Lever AISI 304 1 4301 7...

Страница 7: ...of contaminating fluids and residues or mechanical damage that may represent a health safety or environmental risk must be provided in writing by the distributors and costumers when returning products...

Отзывы: