1.4 Installation
Installation must only be carried out by properly qualified personnel.
Make sure that the main electrical supply in the installation room is disconnected before starting the electrical
operations of assembly.
The appliance must not be installed near curtains, drapes, etc. as these could compromise the correct working
of the product.
Make sure that, once installed, the fan blades are placed not less than 2.30 m away from the floor below to the
product. In case of installation of more than one appliance, the distance between the products must be at least 3 m.
Before assembling or using this product, carefully read all the instructions in this manual and be sure to own all
the necessary material for the installation.
Scrupulously follow the instructions in this manual.
Assembly instructions
EXT
INT
min = 2,30 m
6
1° - 2°
ØD
1)
Once the area of installation is selected, mark the center of
the hole to be made on the wall.
Make sure that on internal and external walls there is
enough space, for a radius of 150 mm from the center, thus
corresponding to the product overall dimensions. Therefore
make sure that, within this area, there are not interferences
with other walls or non-removable objects.
Hole for installation is: Ø 160 mm.
The duct must be installed through the hole, with a slight
downward slope of 1° - 2° towards the outsight to allow
proper discharge of condensation.
To use the supplied recessed duct, the thickness of the wall
must not exceed 400 mm.
To install the product, the wall thickness cannot be less than
250 mm.
Obtained the hole, put the recessed duct (6) into the wall.
M=?
EXT
INT
min = 2,30 m
2)
Make sure that the length of the recessed duct (6) is equal
to the thickness of the wall.
The duct must end with the internal and external surfaces of
the wall.