![Valrom Industrie aquaPUR SOFT 18 Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/valrom-industrie/aquapur-soft-18/aquapur-soft-18_handbook-of-installation-and-operation_3278442042.webp)
42
technical characteristics”)
Water hardness = 15 ºG
Regeneration Meter Setting between 2 regenerations = Cyclic capacity / Hardness = 75/15 = 5 [m³]
After making the calculation, in the respective window, the obtained result is to be introduced under
Capacity. When scrolling within the window you should use the same procedure as under item
"3.4.1.".
!
At this point the station is functional. The following settings are addressed to authorized personnel.
3.4.5. Stepwise regeneration
A resin regeneration cycle is made up of several steps in the following order:
• Backwash
• Brine draw
• Rinse
• Refil
When accessing this parameter by means of key SET „■”, you may achieve, on choice, subject to the
respective need, only one of the steps of a regeneration cycle, namely:
For a start, the valve will automatically begin with the Backwash step opening the following window:
If none of the valve keys is pressed then the valve will complete the Backwashing step
(30 minutes) and return to the MAIN MENU without going on with the remaining steps.
If during the time the valve achieves the Backwash step you press any valve key, this one will pass on to
the next step, showing:
If none of the valve keys is pressed then the valve will complete the Brine Drawing step
(60 minutes) and return to the MAIN MENU without going on with the remaining steps.
If during the time the valve achieves the Brine Drawing step you press any valve key, this one will pass
on to the next step, showing:
If none of the valve keys is pressed then the valve will complete the Rinsing step (30 minutes) and return
to the MAIN MENU without going on with the remaining steps.
If during the time the valve achieves the Rinsing step you press any valve key, this one will pass on to the
next step, showing:
Backwashing...
Any Key to Cancel
Rinsing...
Any Key to Cancel
Refilling...
Any Key to Cancel