9
2.16
Propane gas appliances must not be installed in a room which is built
entirely below ground level (see BS 5871 Part 2).
2.17
A concealed gas supply connection can be made through grommet near
the right corner of the rear panel. Visible front connection can be from the left
or right side.
2.18
Electrical connection to the isolating switched fused spur is from the left
side.
2.19
The flue terminal should be located so that the wind can blow freely
across it at all times and where any blockage due to leaves, snow, etc. is unlikely.
The minimum allowable distances from the terminal are shown in the
following table and figure 3.
Note: The distances are from the edge of the vertical exit
slots in the terminal
not from the edges of the rectangular box (See figure 3a).
Dimension
Terminal Position
Minimum
Distance
A
Directly below an opening, air brick, windows,
etc.
300mm
B
Below gutters, soil pipes or drain pipes
75mm
C
Below eaves
200mm
D
Below balconies or car port roof
200mm
E
From a vertical drain pipe or soil pipe
75mm
F
From an internal or external corner
200mm
G
Above ground, roof or balcony level
300mm
H
From a surface facing the terminal
600mm
I
From a terminal facing the terminal
1200mm
J
From an opening in a car port (e.g. door,
window) into dwelling
1200mm
K
Vertically from a terminal on the same wall
1500mm
L
Horizontally from a terminal on the same wall
300mm
M
Projection outwards from wall
50mm
2.20
This appliance is supplied with a terminal guard. In England and Wales,
the Building Regulations require that the terminal guard is fitted if the flue
terminal can come in contact with people near the building or be subject to
damage. Even if the regulations do not demand it, we recommend that the
guard is fitted to prevent damage or blockage of the flue system by leaves etc.
Fig. 3
Minimum distances for
terminal positions shown
in the table are from slot
openings
Fig. 3a