3” Liners
3” min.
Bend
Radius
Typical Vent Installation
See list of approved Venting Accessories on page 41 of this
manual.
NOTE: Flexible co-linear vent pipes may only be installed
into existing non-combustible solid-fuel burning fi replaces
and chimneys.
Vent Location
The vent terminal must be located through the roof. This direct
vent appliance is designed to operate when an undisturbed
airfl ow hits the outside vent terminal from any direction.
Check local codes for allowable vertical vent termination.
Venting Table
Maximum vertical height 40 ft (measured to bottom of termination)
Minimum vertical height
10 ft (measured to bottom of termination)
Maximum horizontal run
4 ft (measured center to center of pipe)
Maximum off set angle
45˚ (sweeping bend to allow for obstructions)
Venting Notes
Where possible, avoid joining fl ex pipes. If joints are required,
use a approved connector and seal joints with
RTV high temp
sealant
.
Horizontal off set is permissible to allow for routing around
masonry projections. Avoid bending fl ex pipe over a 45
degrees radius where possible.
Terminal Cap
Flashing
2 x 3” fl ex
liners—see
Venting Table
for length
allowed
Existing
fi replace
and
chimney
QUALIFIED
INSTALLER
23
Venting
Содержание Legend G4 Series
Страница 46: ......