Page 29
©
GDC Group Ltd. SEPT 2018
14.6 Check inlet pressure.
The appliance is pre-set to give the correct heat input
at the inlet pressure shown in section 4 of this guide.
1.
Ensure that the fire is
OFF
then fit a pressure
gauge at the test point. The test point is on the inlet ‘T’
connector. Turn the fire ON and check the pressure
with the appliance alight and set at maximum output.
2.
After checking, turn off the appliance. Remove the
pressure gauge and replace the test point sealing
screw.
3.
Test around the sealing screw for gas soundness
with a suitable leak detection fluid.
15.
REASSEMBLE OF FIRE & LOG SET LAYOUT
The remaining parts that where removed earlier now need to be refitted;
15.1
Secure the burner unit into the convector box using the screws removed earlier.
15.2
The top tray requires screwing back in position.
15.3
Install the log set and decorative components supplied
15.3.1
Fit the 4 small logs as shown in the picture. Two fit at the rear and the other
two at the front running back between the 3 burner tubes.
INSTALLER GUIDE