Installation to a timber framed building should be in accordance with the relevant
sections of Institute of Gas Engineers publication IGE/UP/7 “Gas installations in
timber frame buildings”. 

Please note that advice should be sought before installing in a

timber frame building since the alterations required may nullify any NHBC cover relating
to the property. If in doubt, guidance should be requested from your local authority
planning or building department.

This appliance must be mounted with a non-combustible hearth (N.B. conglomerate
marble hearths are considered as non-combustible). The fire box must be mounted on a
non-combustible surface level with the hearth. The hearth must project at least 345mm
forward of the fire box front and be at least 625mm wide (see illustrations in “wall
preparation” section). The hearth material must be at least 12mm thick.  The periphery
of the hearth (or fender) should be at least 50mm above floor level to discourage the
placing of carpets or rugs over it.
The surface of the hearth must be sufficiently flat to enable the bottom of the front
casting to be aligned horizontally. Any excessive unevenness (uneven tiles, Cotswold
stone, etc.) should be rectified.

The appliance must not stand on combustible materials or carpets.
The appliance must not be fitted directly against a combustible wall. 

If the

appliance is to be fitted against a wall with combustible cladding or skirting board, such
materials must be removed from the area covered by the metal outer surround of the
appliance. We suggest that the actual surround is used as a template to mark the area for
combustible cladding removal.
The appliance can be fitted to
a purpose made proprietary
class “O” 150°C surround.
The opening in the surround
or wall recess for the fire box
must be within the limits
shown in figure 1.

The front face of the wall
should be reasonably flat over
the area which will be covered
by the fire box top and side
flanges  to ensure a good seal.
The minimum height from
the top surface of the hearth to
the underside of any shelf
made from wood or other
combustible materials is as
follows:-

 

For a shelf up to 150mm

deep

Minimum height = 750mm.

 

For a shelf deeper than 150mm

Minimum height = 750mm + 12.5mm for every 25mm depth over 150mm.

Note that soft wall coverings (e.g. embossed vinyl, etc.) are easily affected by heat. They
may scorch or become discoloured when close to a heating appliance.  Please bear this
in mind when installing.

The appliance must not be installed in any room which contains a bath or shower or
where steam is regularly present.

An extractor fan may only be used in the same room as this appliance, or in any area
from which ventilation for the appliance is taken, if it does not affect the safe
performance of the appliance. Note the spillage test requirements detailed further on in
this manual. If the fan is likely to affect the appliance, the appliance must not be
installed unless the fan is permanently disconnected, or provision is made to ensure that
the fan and the appliance cannot be used at the same time.

 

Fig. 1 Hearth & Recess Requirements

Содержание COSYFLAME TURBOCHIM 528

Страница 1: ...HIM M O D E L 5 2 8 VALOR SECRET TURBOCHIM M O D E L 5 2 7 HEARTHMASTER M O D E L 5 2 7 w R e a r F a n F l u e d I n s e t G a s F i r e s w i t h L i v e F u e l E f f e c t I N S T A L L E R G U I...

Страница 2: ...d our Valor AdviceLine will be pleased to help Please telephone 0345 626341 Local call rates apply P l e a s e l e a v e t h i s I n s t a l l e r G u i d e w i t h t h e u s e r This appliance is for...

Страница 3: ...r unit 17 Electrical test 18 Terminal guarding 18 PART 7 GAS SUPPLY INSTALLATION 19 Preliminary Burner Checks 19 Check Reference Pressure 20 PART 8 FITTING THE CERAMICS 20 PART 9 CHECKS 22 Recheck Con...

Страница 4: ...ring Regulations BS7671 In the United Kingdom the installation must also be in accordance with a All the relevant parts of local regulations b The current edition of the Building Regulations issued by...

Страница 5: ...be removed from the area covered by the metal outer surround of the appliance We suggest that the actual surround is used as a template to mark the area for combustible cladding removal The appliance...

Страница 6: ...rojection outwards from wall 55mm Fig 2 Allowable Terminal Positions A fan powered flue system tends to depressurise the room containing the appliance Normally no additional ventilation should be requ...

Страница 7: ...ntact with people near the building or be subject to damage Even if the regulations do not demand it we recommend that the guard is fitted to prevent damage or blockage of the flue system by leaves et...

Страница 8: ...tion 205mm when sited outside wall 55mm when recessed in outer wall P 285mm R Flue tube diameter 125mm S Terminal guard projection 305mm T 355mm V Recess width 390mm min 425mm max W Recess depth 140mm...

Страница 9: ...d pressure switch loom 2 Rolls aluminium tape Fig 4 Appliance units 1 Nut olive for 8mm inlet pipe 1 Retention kit 4 wall plugs 4 eye bolts 2 tension adjusters and two cable assemblies 10 Wall plugs 1...

Страница 10: ...izes as close to the minimum dimensions as possible in order to minimise the sealing required Make sure that the or any electrical wiring piping etc in the wall is not affected when cutting the instal...

Страница 11: ...removing the masonry and clearing debris If the cavity has loose fill e g granular insulation material pack the edges of the opening with Rockwool as you proceed to hold back the insulating material...

Страница 12: ...meter circle for the flue hole Chisel out the area marked It may be necessary to make good both the internal and external wall faces To achieve a neat finish and to make any future removal of the flue...

Страница 13: ...n the flue hole to ensure that there is adequate clearance for both the flue tube and the electrical loom A trial installation of both is recommended The groove should be cut in the lower left hand si...

Страница 14: ...ng method is to be used in which case tape up after cables are in position Now connect the wiring loom at the firebox end the eight pin connector is located on the lower left hand side of the applianc...

Страница 15: ...lts Return the cables through the holes provided at the lower back of the firebox Assemble adjusters and tension as in figure 17 Securing firebox to wall using fixing brackets Loose assemble the two f...

Страница 16: ...ted in the flue pipe Ensure the box is firmly located and correctly aligned against the wall and mark off the four screw fixing positions on the wall Remove the fanbox Drill at the market positions fo...

Страница 17: ...loom now connected the enclosure can be replaced as shown in figure 24 Locate the cable loom earth tags and secure to the fan box earth stud using the M4 nut and shakeproof washer supplied Connect the...

Страница 18: ...n approximately two seconds iii Remove the hand The fan should revert to normal speed after approximately three seconds The unit includes a blocked flue sensor system To check its operation i Switch t...

Страница 19: ...ut Release the on switch The fan should continue to run Depress the control knob and turn anticlockwise partially towards the PILOT IGN position until some resistance is felt Keep depressed at this po...

Страница 20: ...ition and test around the sealing screw for gas soundness with a suitable leak detection fluid Do not use leak detection sprays on this appliance Sprays may affect the operation of electrical componen...

Страница 21: ...her coals are installed Place four of the medium size coals in the four valleys of the front coal Place the left side coal so that the customer will be able to see the pilot flame See figures 37 and 3...

Страница 22: ...ible When pilot ignition has been achieved keep the control knob depressed for approximately ten seconds to allow the thermocouple probe to warm up and then release it If the pilot does not remain ali...

Страница 23: ...nue with the installation If the test is not satisfactory Disconnect the appliance and seek expert advice If any other non sealed gas appliances are installed in connecting rooms check to ensure that...

Страница 24: ...liance has a flame failure spillage monitoring system Point out the explanation of this system shown in the owner s guide under Operating the Fire Advise that if the fire goes out for any reason wait...

Страница 25: ...e of the plaque must touch the inside edge of the retaining flange at the left side of the burner well Place the new right hand plaque in position Fit a new centre gasket between the plaques If there...

Страница 26: ...nit clear To separate the tap from the solenoid detach the solenoid unit at the gas tap end Replace in the reverse order To Remove The Piezo Generator Remove the gas tap FSD solenoid unit as described...

Страница 27: ...connector at the fan motor casing Withdraw the fan unit from the fan box taking care not to snag or damage the wiring loom See figure 52 Replace in reverse order To remove the pressure switch Access t...

Страница 28: ...360 1 545959 D Gas tap spark generator 1 545969 E Spark generator 1 521069 F Control knob 1 545979 G Pilot unit 1 545949 H Solenoid valve 1 559719 J Burner plaque gasket set 1 545989 K On switch 1 55...

Страница 29: ...t Standards Valor is a member of the Society of British Gas Industries which works to ensure high standards of safety quality and performance Careful Installation Valor is a Corgi registered company A...

Отзывы: