Valor COSYFLAME TURBOCHIM 528 Скачать руководство пользователя страница 12

12

Wall preparation for flue tube.

The flue must be installed so that it is at right angles to the back panel of the fire all
round the flue circumference.  The fire itself should be fitted vertically against a flat
wall.  Where this is difficult to achieve due to building inaccuracies care should be taken
to ensure that the back of the fire is not stressed in any way due to distortion of the
assembly when tightening the fixing screws. Where necessary, non-combustible packing
pieces should be used to provide a satisfactory fixing surface.
Before cutting the hole in the wall make sure that the height to the top surface of the
finished floor is known.  The height from this surface to the flue hole centre is shown
in figure 13.
If a loose hearth or plinth is to be used, the height from its top surface must be used
when determining the flue height.
Place dust sheets on the floor and over any furnishings etc.
Make sure that the centre of the flue hole is as shown in figure

 

13.

Now cut the hole for the flue unit.

Core drilling

Drill a pilot hole through the wall.  Inspect the hole to ensure that it is in the brickwork
and not in mortar.  If it is in mortar, it is advisable to reposition the hole approximately
25mm away (Ensuring that all other clearances to firebox are complied with.).
Remember to reposition the screw fixing holes.
Drill the flue hole with a 5in. (127mm) core drill.
Remove any combustible wall cladding material from the area behind the firebox as
described previously.

Hammer and chisel cutting

Mark a 127mm (5in) diameter circle for the flue hole.  Chisel out the area marked.
It may be necessary to make good both the internal and external wall faces.  To achieve
a neat finish and to make any future removal of the flue unit easier, it is recommended
that a cardboard cylinder is formed around the flue unit and inserted in the hole whilst
making good.  Remove the cardboard cylinder after making good.

Combustible walls (wood, fibreboard,
plasterboard etc.)

Building regulations require that the outer surface of the
flue tube and terminal must not be closer than 25mm to
combustible material and must be lined with steel sleeve not
less than 0.5mm thick. (see figure 12). The sleeve can be
made  by coiling a piece of sheet steel to between 125mm &
127mm outside dia.and fitting it to the combustible parts of
the construction.
Mark out and cut a hole 177mm diameter through the
plasterboard. Cut a hole of about 165mm in the vapour
barrier. Clear the insulation quilt from the hole area and cut
a 177mm dia. hole in the timber sheathing and breather
paper.   Drill a 127mm diameter hole through a non-
combustible (brick etc.) outer wall.
Fit the steel sleeve. The sleeve should not protrude more
than 10mm into the cavity.  The sleeve should be sealed to
the inner leaf of the wall at both ends with a non-setting
thermal mastic sealant.
If the outer wall is combustible drill a 177mm hole and fit
the  liner sleeve through to this wall.
Cover the hole with a steel plate size 500mm x 235mm, not
less than 1.5mm thick with a 127mm diameter hole in the

middle. Fix with suitable screws and plugs.
Where the whole wall is of combustible material a non-corrosive plate 455mm square
with a 127mm diameter hole in the centre must be fitted to the outer face of the wall.

 Fig. 12

Содержание COSYFLAME TURBOCHIM 528

Страница 1: ...HIM M O D E L 5 2 8 VALOR SECRET TURBOCHIM M O D E L 5 2 7 HEARTHMASTER M O D E L 5 2 7 w R e a r F a n F l u e d I n s e t G a s F i r e s w i t h L i v e F u e l E f f e c t I N S T A L L E R G U I...

Страница 2: ...d our Valor AdviceLine will be pleased to help Please telephone 0345 626341 Local call rates apply P l e a s e l e a v e t h i s I n s t a l l e r G u i d e w i t h t h e u s e r This appliance is for...

Страница 3: ...r unit 17 Electrical test 18 Terminal guarding 18 PART 7 GAS SUPPLY INSTALLATION 19 Preliminary Burner Checks 19 Check Reference Pressure 20 PART 8 FITTING THE CERAMICS 20 PART 9 CHECKS 22 Recheck Con...

Страница 4: ...ring Regulations BS7671 In the United Kingdom the installation must also be in accordance with a All the relevant parts of local regulations b The current edition of the Building Regulations issued by...

Страница 5: ...be removed from the area covered by the metal outer surround of the appliance We suggest that the actual surround is used as a template to mark the area for combustible cladding removal The appliance...

Страница 6: ...rojection outwards from wall 55mm Fig 2 Allowable Terminal Positions A fan powered flue system tends to depressurise the room containing the appliance Normally no additional ventilation should be requ...

Страница 7: ...ntact with people near the building or be subject to damage Even if the regulations do not demand it we recommend that the guard is fitted to prevent damage or blockage of the flue system by leaves et...

Страница 8: ...tion 205mm when sited outside wall 55mm when recessed in outer wall P 285mm R Flue tube diameter 125mm S Terminal guard projection 305mm T 355mm V Recess width 390mm min 425mm max W Recess depth 140mm...

Страница 9: ...d pressure switch loom 2 Rolls aluminium tape Fig 4 Appliance units 1 Nut olive for 8mm inlet pipe 1 Retention kit 4 wall plugs 4 eye bolts 2 tension adjusters and two cable assemblies 10 Wall plugs 1...

Страница 10: ...izes as close to the minimum dimensions as possible in order to minimise the sealing required Make sure that the or any electrical wiring piping etc in the wall is not affected when cutting the instal...

Страница 11: ...removing the masonry and clearing debris If the cavity has loose fill e g granular insulation material pack the edges of the opening with Rockwool as you proceed to hold back the insulating material...

Страница 12: ...meter circle for the flue hole Chisel out the area marked It may be necessary to make good both the internal and external wall faces To achieve a neat finish and to make any future removal of the flue...

Страница 13: ...n the flue hole to ensure that there is adequate clearance for both the flue tube and the electrical loom A trial installation of both is recommended The groove should be cut in the lower left hand si...

Страница 14: ...ng method is to be used in which case tape up after cables are in position Now connect the wiring loom at the firebox end the eight pin connector is located on the lower left hand side of the applianc...

Страница 15: ...lts Return the cables through the holes provided at the lower back of the firebox Assemble adjusters and tension as in figure 17 Securing firebox to wall using fixing brackets Loose assemble the two f...

Страница 16: ...ted in the flue pipe Ensure the box is firmly located and correctly aligned against the wall and mark off the four screw fixing positions on the wall Remove the fanbox Drill at the market positions fo...

Страница 17: ...loom now connected the enclosure can be replaced as shown in figure 24 Locate the cable loom earth tags and secure to the fan box earth stud using the M4 nut and shakeproof washer supplied Connect the...

Страница 18: ...n approximately two seconds iii Remove the hand The fan should revert to normal speed after approximately three seconds The unit includes a blocked flue sensor system To check its operation i Switch t...

Страница 19: ...ut Release the on switch The fan should continue to run Depress the control knob and turn anticlockwise partially towards the PILOT IGN position until some resistance is felt Keep depressed at this po...

Страница 20: ...ition and test around the sealing screw for gas soundness with a suitable leak detection fluid Do not use leak detection sprays on this appliance Sprays may affect the operation of electrical componen...

Страница 21: ...her coals are installed Place four of the medium size coals in the four valleys of the front coal Place the left side coal so that the customer will be able to see the pilot flame See figures 37 and 3...

Страница 22: ...ible When pilot ignition has been achieved keep the control knob depressed for approximately ten seconds to allow the thermocouple probe to warm up and then release it If the pilot does not remain ali...

Страница 23: ...nue with the installation If the test is not satisfactory Disconnect the appliance and seek expert advice If any other non sealed gas appliances are installed in connecting rooms check to ensure that...

Страница 24: ...liance has a flame failure spillage monitoring system Point out the explanation of this system shown in the owner s guide under Operating the Fire Advise that if the fire goes out for any reason wait...

Страница 25: ...e of the plaque must touch the inside edge of the retaining flange at the left side of the burner well Place the new right hand plaque in position Fit a new centre gasket between the plaques If there...

Страница 26: ...nit clear To separate the tap from the solenoid detach the solenoid unit at the gas tap end Replace in the reverse order To Remove The Piezo Generator Remove the gas tap FSD solenoid unit as described...

Страница 27: ...connector at the fan motor casing Withdraw the fan unit from the fan box taking care not to snag or damage the wiring loom See figure 52 Replace in reverse order To remove the pressure switch Access t...

Страница 28: ...360 1 545959 D Gas tap spark generator 1 545969 E Spark generator 1 521069 F Control knob 1 545979 G Pilot unit 1 545949 H Solenoid valve 1 559719 J Burner plaque gasket set 1 545989 K On switch 1 55...

Страница 29: ...t Standards Valor is a member of the Society of British Gas Industries which works to ensure high standards of safety quality and performance Careful Installation Valor is a Corgi registered company A...

Отзывы: