10
10
Horizontal Termination Venting Con
fi
gurations
See venting accessories list on pages 32–33 for allowable components.
Rear Outlet—No Vertical Rise
Flat on the Wall
Maximum 26” horizontal pipe length;
817VAK Vent Collar Adapter required if using other
than Valor’s 551DVK pipe with termination;
Terminal Guard may be required if terminating within
7’0” of grade or where accessible.
In Corner—No Vertical Rise
Maximum 1 x 45° elbow allowed;
Maximum 18” horizontal pipe length;
Terminal guard may be required if terminating within
7’0” of grade or where accessible.
•
•
•
•
•
•
Approved
trough wall
shield/thimble
Approved
side wall
termination
530
engine
Max. 26” (66 cm)
14” (36 cm) max.
within
combustible wall.
26” (66 cm) max.
vent length
Approved
through wall
shield/thimble
Approved
side wall
termination
530
engine
18” (46 cm)
max vent pipe