Valor 530 B Vent Скачать руководство пользователя страница 12

12 of 18 

9.  GAS SUPPLY INSTALLATION 

1.

 

The appliance is supplied for supply gas connection at the rear left corner of the case. An adapter 

is  included  in  the  pack  that  must  be  fitted  to  the  appliance  inlet  pipe.  Supply  line  connection  to  the 
adapter is 

3

/

8

”NPT. 

Alternatively, the appliance inlet pipe may be removed and the supply line routed directly to the control 
unit. An isolating valve could be fitted within the appliance case. If the circulating fan is to be installed, 
be aware that the supply pipe should follow the route of the original appliance inlet pipe in order to 
clear the fan. If intending to fit an internal isolating valve, check that it will be clear of the fan. 
2. 

Use  only  new  black iron or steel pipes or copper tubing if acceptable - check local codes. Note 

that in USA copper tubing must be internally tinned for protection against sulfur compounds. 
3. 

Unions in gas lines should be of ground joint type. 

4. 

The gas supply line must be sized and installed to provide a supply of gas sufficient to meet the 

maximum demand of the appliance without undue loss of pressure. 
5. 

Sealant  used  must  be  resistant  to  the  action  of  all  gas  constituents  including  LP  gas.  Sealant 

should be applied lightly to male threads to ensure excess sealant does not enter gas lines. 
6. 

The supply line should include a manual shut-off valve to allow the appliance to be disconnected 

for servicing.  
A plugged 1/8”NPT tapping must be installed in the line. The tapping must be accessible for test gauge 
connection and be immediately upstream of the gas supply connection to the appliance. 
7. 

Pressure test the supply line for leaks. 

• 

The appliance and its individual shut-off valve must be disconnected from the gas supply piping 
system during any pressure testing of that system at test pressures in excess of ½psig (3.5kPa). 

• 

The  appliance  must  be  isolated  from  the  gas  supply  piping  system  by  closing  its  individual 
manual  shut-off  valve  during  any  pressure  testing  of  the  gas  supply  piping  system  at  test 
pressures equal to or less than ½psig (3.5kPa). 

• 

Failure  to  either  disconnect  or  isolate  the  appliance  during  pressure  testing  may  result  in 
regulator or valve damage. Consult your dealer in this case. 

8. 

The minimum supply pressure is given in section 3 of this manual. 

9

All piping and connections must be tested for leaks after installation or servicing. All leaks must 

be corrected immediately. 
When testing for leaks: 

• 

Make sure that the appliance is turned off. 

• 

Open the manual shut-off valve. 

• 

Test  for  leaks  by  applying  a  liquid 
detergent  or  soap  solution  to  all  joints. 
Bubbles  forming  indicate  a  gas  leak. 
Never  use  an  open  flame  to  check  for 
leaks.
 

Correct any leak detected immediately. 
10. 

The  pressure  test  tapping  locations  are 

shown  in  figure  19.  A  built-in  non-adjustable 
regulator controls the burner manifold pressure. 
The correct pressure range is shown in the table 
in section 3 of this manual. The pressure check 
should be made with the burner alight and the thermostat at its highest setting. See lighting instruction 
section for full operating details.  

 

  
 Figure 19 

Содержание 530 B Vent

Страница 1: ...GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s ins...

Страница 2: ...flame control motor 7 B Vent Conversion Kit Installation 8 Attaching top air deflector 9 7 VENTING APPLIANCE FIXING 10 Preparing for Floor Fixing 10 Venting 10 8 FITTING SIDES SWITCH 11 9 GAS SUPPLY...

Страница 3: ...nd free from combustible materials gasoline and other flammable vapors and liquids Keep the vent unit and connector at the back of the heater at least 3inches from any combustible surfaces Keep the B...

Страница 4: ...ireplace is installed or retrofitted at a later date Kit 553RCK Circulating fan Having variable speed and temperature control it is designed to boost the natural convection process through the applian...

Страница 5: ...0 When converted using kit 554LPK Tested to CAN CGA 2 17 Gas fired appliances for use at high altitudes In the USA installations may require deration over 2000ft Check local codes 3 LOCATION The Presi...

Страница 6: ...lations 552BVK B Vent Conversion Kit 1 B vent adapter unit with vent switch 1 Thermocouple interrupter 1 Case rear cover plate 2 P clips for wire fastening 531CSB 532ESB 533ESG President Free Standing...

Страница 7: ...de unit is at the left end of the burner Push in the lighting knob and turn counter clockwise through the IGN position to PILOT A spark should flash across from the pilot electrode to the pilot burner...

Страница 8: ...ed The hole in the cover plate must be nearest the top edge See figure 6 3 Remove 4 screws from the case back 2 each side just outside of the cover plate Fit the adapter unit to the case using these s...

Страница 9: ...rmocouple into the interrupter block until finger tight Make sure that the wires are properly located and finally tighten the thermocouple nut with a wrench to secure the wires with good contact See f...

Страница 10: ...ry Venting Reposition the appliance in its final location Connect an approved 4 vent unit to the adapter collar Install the vent unit in accordance with the instructions supplied with the unit If inst...

Страница 11: ...in figure 15 Fit the batteries supplied with the engine unit to the holder supplied with the wall switch Fit the wall switch plate to your switch box c For active remote control Caution Don t connect...

Страница 12: ...ed in the line The tapping must be accessible for test gauge connection and be immediately upstream of the gas supply connection to the appliance 7 Pressure test the supply line for leaks The applianc...

Страница 13: ...g will give optimum performance and should not be altered In a few unusual installations performance may be improved by adjusting the aeration The need for adjustment should be determined by operating...

Страница 14: ...he rear wall by loosening the channel securing screws and adjusting the position of the channels See figure 22 3 Remove two screws from under the top front of the firebox Using these screws fit the po...

Страница 15: ...his log on the projection at front center of the base log It is important that the narrow nose does not drop down to touch the burner See figure 27 8 Place the left side log on base log at the left si...

Страница 16: ...appliance rocker switch wall switch remote hand unit See owner s lighting instructions further on in this manual for full details Aeration adjustment As described in section 11 burner aeration is adj...

Страница 17: ...ing in the B vent adapter box See figure 32 The installation is satisfactory if the majority of the smoke is drawn into the adapter box and up to the vent pipe If the vent is blocked or has strong rev...

Страница 18: ...shown in figure 33 2 Fit the top casting making sure that the corners locate as shown in figure 34 3 Fit the top infill casting See figure 35 4 If necessary the appliance can be leveled by the adjustm...

Отзывы: