11.  SERVICING & PARTS REPLACEMENT

Always turn off the gas supply and allow the appliance to cool completely
before commencing any servicing (The appliance inlet “T” connector
incorporates an isolating valve).

It is recommended that, at least once a year, the appliance is disconnected
and the catchment space behind the closure plate checked and cleared of
any debris. The closure plate must be resealed to the wall after checking.

Check that soot or debris is not impairing the electrode spark or pilot burner.

Check that soot or debris is not blocking any of the holes in the main burner.

Always test for gas soundness and spillage after servicing the appliance.

11.1 To replace radiant(s).

1.

Remove the dress guard by gently pulling it in the centre with one hand, and

carefully springing out one end from the fascia with the other. Slide the opposite side
of the dress guard clear of the fixing holes.

Take care not to scratch the trim (See

figure 17).

2. 

Remove the old radiant(s). Fit the

new radiant(s) ensuring that their rear
face rests against the horizontal ribs
in the rear panel. There will be a
small gap between their bottom front
edges and the retaining channel at
the front of the radiant box.

3. 

Replace the dress guard.

11.2 To remove the fascia.

1. 

Remove the two fascia retaining

screws located at the bottom rear of
the fascia. 

2. 

Lift the fascia up and forward to

clear the rear top location.

3. 

Replace in the reverse order. Make

sure that the top rear of the of the
fascia locates fully into the ‘U’ shaped
notch of the engine back panel (See figure15). Make sure that the radiants are not
dislodged when refitting the fascia.

Page 29

© 

Baxi Heating U.K. Limited 2009.

Figure 17.

INSTALLER GUIDE

Содержание 348 Brava

Страница 1: ...IDE We trust that this guide gives sufficient details to enable this appliance to be installed and maintained satisfactorily However if further information is required our Valor Fires Technical Helpli...

Страница 2: ...of the proposed use to the following address The Company Secretary Baxi Heating UK Limited The Wyvern Business Park Stanier Way Derby DE21 6BF Warning Any person who does any unauthorised act in rela...

Страница 3: ...ISO 9001 quality system accepted by the British Standards Institute The Highest Standards Valor Fires is a member of SBGI and HHIC Heating and Hot water Industry Council that work to ensure high stand...

Страница 4: ...Baxi Heating U K Limited 2009 Page 4 INSTALLER GUIDE FOR OWNER GUIDE SEE PAGES 34 TO 47 INSTALLER GUIDE...

Страница 5: ...iderations 10 4 5 Chimney preparation 10 4 6 Fireplace preparation 11 4 7 Fireplace clearances 12 4 8 The Flue spigot 13 4 9 The hearth 14 4 10 Installation options 14 4 11 Flues 16 5 PRE INSTALLATION...

Страница 6: ...T 29 11 1 To replace radiant s 29 11 2 To remove the fascia 29 11 3 To remove the electronic igniter unit 30 11 4 To remove the pilot unit 30 11 5 To remove the injectors 30 11 6 To remove the burner...

Страница 7: ...ht Bend your legs and not your back Avoid twisting at the waist It is better to reposition your feet Avoid upper body top heavy bending Do not lean forward or sideways whilst handling the fire Always...

Страница 8: ...fficiency value may be used in the UK Government s Standard Assessment Procedure SAP for energy rating of dwellings The conversion of net efficiency to gross was achieved by multiplying the net effici...

Страница 9: ...of rated input not exceeding 70 kW net 1st 2nd and 3rd family gases Specification for installation of gas appliances to chimneys and for maintenance of chimneys BS 5440 Part 2 Installation and mainten...

Страница 10: ...e A S D will shut the appliance down if an unacceptable amount of harmful products of combustion accumulate Under no circumstances should the A S D be altered or bypassed in any way Only genuine manuf...

Страница 11: ...to that of the closure plate plus 20mm and for a width equal to that of the closure plate plus 40mm 4 6 4 If the fire is to be fitted against a wall with combustible cladding the cladding must be rem...

Страница 12: ...erating the slider control 4 7 2 Allow a minimum clearance of 95mm from the top surface of the appliance fascia to the underside of any shelf whether it is made from combustible or non combustible mat...

Страница 13: ...back of the closure plate and the back of the catchment space On conventional flues the catchment space below the flue spigot must extend at least 250mm downwards measured from the bottom of the flue...

Страница 14: ...When using the baffle the height of the sealing tape and closure plate can be extended to a maximum 630mm before being visible See section 8 2 4 10 2 Precast flues The appliance can be installed to a...

Страница 15: ...e 2 When the additional 50mm minimum is adhered to them the appliance can be fitted without a hearth The wall opening must be within the following dimensions The total height of the closure plate is 6...

Страница 16: ...he baffle the height of the sealing tape and closure plate can be extended to a maximum 630mm before being visible See section 8 2 In addition the fire has been tested for use with a Rite Vent or Selk...

Страница 17: ...BS 5440 Part 1 to ensure that the products of combustion can be safely dispersed into the outside atmosphere Where the appliance is connected to an unlined brick chimney it is generally unnecessary f...

Страница 18: ...ear top location Store in a safe place 5 Remove the radiant pack by gently lifting and pulling forward from the bottom 6 Remove the cardboard strip from the top of the burner area 7 Remove any protect...

Страница 19: ...rom one terminal only and that the termination is suitable Observe where possible upstairs rooms and loft spaces for signs of escaping smoke indicating a defective flue If there is not a definite flow...

Страница 20: ...ng 5 6 2 Fitting the closure plate when wall mounting See figure 10 The closure plate must be fitted and sealed to the hearth and fireplace opening using a suitable heat resistant material If necessar...

Страница 21: ...the fire by loosening the lock nuts and turning the levelling screws in the feet up or down as required while they bear on the hearth When the fire is level and square to the wall retighten the lock n...

Страница 22: ...gap between the cut out and the supply pipe Pressure check the installation pipework for gas soundness In the United Kingdom check in accordance with the current edition of BS6891 In the Republic of...

Страница 23: ...e spillage test In such cases the restrictor will have to be re opened After opening conduct the spillage check again To close the restrictor 1 Loosen the screw situated behind the cut out in the blac...

Страница 24: ...tically spring up and the centre radiants should be fully on If the flames go out at this stage or when checking the rest of the setting positions try the full lighting sequence again If the flames fa...

Страница 25: ...nly be exchanged using authorised parts 3 Set the slider to the off O position 4 Open the isolating valve on the inlet T connector Screw on the end cap and test for leaks 7 3 Check reference pressure...

Страница 26: ...um 630mm At the rear top corners of the fascia there are two screws one at each side Loosen the screws but do NOT remove them Locate the baffle onto the screws as in figure 14 The baffle is angled and...

Страница 27: ...sealing is satisfactory but the appliance is installed with the flue restrictor in the closed position See section 6 5 reopen the restrictor reseal the appliance and retest If smoke is still not draw...

Страница 28: ...that any cleaning must only be carried out when the fire is off and cold Advise the customer that they should read the owner guide before operating the fire and always follow the advice in the sectio...

Страница 29: ...with one hand and carefully springing out one end from the fascia with the other Slide the opposite side of the dress guard clear of the fixing holes Take care not to scratch the trim See figure 17 2...

Страница 30: ...le 2 Once removed ensure that the dust cage is cleaned before refitting 11 5 To remove the injectors 1 Remove the fascia as in section 11 2 2 Support the injector carrier to avoid straining the pipe w...

Страница 31: ...se damage 7 Unscrew and remove the three screws from the rear of the assembly See figure 17 8 Detach the left end of the burner module from the radiant box by removing one screw and a wing nut See fig...

Страница 32: ...flow rate controller as in section 11 8 2 Unscrew and remove the upper injector pipe 3 Loosen the locking nut where the T piece joins the shut off valve 4 Unscrew the T piece 5 Refit in the reverse or...

Страница 33: ...he shut off valve 8 Remove the two screws from the head of the tap 9 Rotate the plug and pull it out of the tap 10 Clean and grease the plug lightly with suitable grease Do not apply excessive grease...

Страница 34: ...Page 34 Baxi Heating U K Limited 2009 OWNER GUIDE OWNER GUIDE FOR WARRANTY AND SERVICE INFORMATION SEE PAGES 43 TO 47...

Страница 35: ...ANCE 42 Battery replacement 42 Regular maintenance 42 WARRANTY AND SERVICE 43 This gas fire is designed to meet the most stringent quality performance and safety requirements to provide you with many...

Страница 36: ...erside of any shelf whether it is made from combustible or non combustible materials This clearance is necessary to allow the fascia to be lifted off for servicing and also allows sufficient access to...

Страница 37: ...dards it is a heating appliance and certain parts of its surface will become hot Note The guard supplied with the fire acts as a fireguard conforming to BS1945 1971 and satisfies the Heating Appliance...

Страница 38: ...his device incorporates a probe that senses that the heat from the pilot flame is correct If this probe is cool the device will prevent any gas flow unless the control button is held down at the ignit...

Страница 39: ...ould light on their low setting 5 Slide the control button up again to the high H setting you should feel a check to the button movement at this position The outer radiants should now be on their high...

Страница 40: ...w the flame sensing probe to warm up before setting to your preferred heat level For your own convenience have the heater serviced as soon as possible CLEANING YOUR FIRE Turn the fire off and allow it...

Страница 41: ...to clear the metal retaining bar then pull out bottom first Fit the new radiant by inserting its top under the top lip of the radiant box then swing the bottom of the radiant over and behind the retai...

Страница 42: ...ped notch of the engine back panel See figure 6 7 Secure the fascia using the two screws previously removed Regular maintenance In order to achieve and maintain high levels of personal safety and perf...

Страница 43: ...e call on 0844 8711 525 Our promise to you If you experience a fault with your new fire we aim to provide a safe and high quality repair service supported by our dedicated national network of highly s...

Страница 44: ...be of faulty manufacture Free of charge replacement of the complete unit providing the failure is related to a manufacturing fault that cannot be repaired or is uneconomic to repair What this warranty...

Страница 45: ...Baxi Heating U K Limited 2009 Page 45 OWNER GUIDE...

Страница 46: ...d 2009 Page 46 To be completed by installer Installer Details Block Capitals Installer Name Gas Safe Register or Corgi Registration Number Company Name Company Address Company Telephone number Company...

Страница 47: ...ation Fascia name Block Capitals Fascia code Can be found close to the information label Block Capitals Model 3 4 8 Serial number Can be found on the serial number label See figure 7 A LABEL CONTAININ...

Страница 48: ...Baxi Heating U K Limited 2009...

Отзывы: