CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell is clean roughly once a year, 

or whenever the filters are being replaced. Clean by washing 

as required.

IMPORTANT

If the unit has an enthalpy cell, it must not be washed. 

Only aluminium or plastic cells can be washed.

To check and clean the heat recovery cell:

1.   Disconnect the ventilation unit from the mains electricity 

supply.

2.   Lift the latch to open the door of the ventilation unit and 

lift the door off.

CAUTION

The door is heavy.

3.   Remove the filters (A, B, C).

4.  Remove the sealing strip (E) above the cell in the direction 

of the arrow.

5.   Lift and pull the cell (D) out of the unit.

IMPORTANT

Handle the cell carefully! For example, do not lift the 

cell by the layers. The cell layers are very thin and 

easily damaged.

6.   If the cell is dirty, clean it by immersing it in warm water, 

to which a small amount of a mild detergent has been 

added.

7.   Rinse the cell clean with a water spray. Do not use a high-

pressure cleaner.

8.   When all the water has drained from between the layers, 

reassemble the ventilation unit in the reverse order.

9.   Close the door and ensure that the safety switch catch of 

the door is engaged.

10.  Plug the ventilation unit back into the mains. The heat 

recovery cell has now been checked and cleaned.

MAINTENANCE

D

E

D

E

CONDENSING WATER

In the heating season, the extract air humidity condenses to 

water. In new buildings, condensation runoff can form rapidly. 

Condensed water must be able to freely leave the unit. 

At some time before the heating season begins (e.g. during 

autumn maintenance), check that the siphon or the condensing 

water outlet in the bottom pool are not clogged. To check this, 

pour some water into the pool. Clean as required.

NOTE

Some condensing water 

may have accumulated 

in the bottom pool 

of the unit; this is 

normal and requires no 

corrective action. 

WARNING

Water must at all times 

be kept out of the 

electrical system.

Содержание Vallox 90 MV

Страница 1: ...Manual Model Vallox 90 MV Vallox 90K MV Type A3527 A3528 Document D5316 Valid from 30 03 2020 Updated 16 03 2020 Ventilation units MANUAL...

Страница 2: ...mensions and duct outlets 11 MAINTENANCE 12 Vallox 90 MV 90K MV 12 Before beginning maintenance work 12 Changing the filters 12 Cleaning the heat recovery cell 13 Condensing water 13 Cleaning the fans...

Страница 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Страница 4: ...cates a hazard that can result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard th...

Страница 5: ...ws for controlling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation...

Страница 6: ...7 R model in the figure MAIN PARTS Vallox 90 MV Post heating resistor 8 Safety switch 9 Internal humidity sensor 10 Internal carbon dioxide sensor 10 Control panel 11 Carbon dioxide sensor optional 12...

Страница 7: ...istor 8 Safety switch 9 R model in the figure MAIN PARTS Vallox 90K MV Internal humidity sensor 10 Internal carbon dioxide sensor 10 Control panel 11 Carbon dioxide sensor optional 12 Humidity sensor...

Страница 8: ...surface of the ceiling mounting plate and the false ceiling is 14 mm When this minimum distance is used the distance between the top of the unit mounted on the ceiling mounting plate and the ceiling...

Страница 9: ...of the duct that comes to the unit from outside 4 Lift the unit in its place on the ceiling mounting plate until both locking wings 3 lock on the outer edge of the side plate of the unit 5 Visually c...

Страница 10: ...ed the connection cord B at the same time inside the cooker hood 3 Fasten the cooker hood in place with finger nuts 4 Pull the connection cord in place Use line protection C where required Observe in...

Страница 11: ...amper of the HR R model in the figure In the L model the parts are mirrored Dimensions and duct outlets Duct outlets Inner diameter of the female collar 125mm 1 Supply air from the unit to the apartme...

Страница 12: ...he outdoor air Fine filter for supply air filters microscopic pollen and dust particles out of the supply air Coarse filter for extract air filters the extract air and keeps the heat recovery cell cle...

Страница 13: ...to which a small amount of a mild detergent has been added 7 Rinse the cell clean with a water spray Do not use a high pressure cleaner 8 When all the water has drained from between the layers reassem...

Страница 14: ...uching the safety switch 10 Plug the ventilation unit back into the mains Removing and cleaning the extract air fan B To clean the extract air fan 1 Disconnect the ventilation unit from the mains elec...

Страница 15: ...y pressing them 2 Let the bottom plate move to the down position 3 Remove the grease filter from its mountings 4 Clean the grease filter either by washing it with hot water and hand washing detergent...

Страница 16: ...50 52 25 34 41 44 46 49 50 52 2000 17 20 26 31 33 37 39 41 19 25 34 39 41 45 47 49 4000 19 19 20 24 26 30 32 34 19 19 24 29 32 36 38 41 8000 24 24 24 24 24 25 25 26 24 24 24 24 25 27 29 31 LW dB LWA d...

Страница 17: ...odbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output T...

Страница 18: ..._B Local hardware Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O...

Страница 19: ...24V relay output EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different f...

Страница 20: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Страница 21: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Страница 22: ...External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A signal RS_B Local hardware Modbus B signal NTC External t...

Страница 23: ...tion box assembly 3526700 6 HR cell 933070 18 Circuit board mount 3443400 30 NTC sensor kit 946145 6 b Upper sealing slip of the HR cell 3241600 19 Safety switch 948370 31 MyVallox VOC sensor optional...

Страница 24: ...allox humidity sensor optional 946149 6 b Upper sealing slip of the HR cell 3241600 17 Motherboard 949032 1 29 MyVallox carbon dioxide sensor optional 949111 7 Coarse filter for supply air 978028 18 C...

Страница 25: ...CONFORMITY CERTIFICATES...

Страница 26: ...26...

Страница 27: ...27 Vallox Oy All rights reserved...

Страница 28: ...Vallox Oy All rights reserved D5316 16 03 2020FIN 16 03 2020ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270...

Отзывы: