background image

13

© Vallox Oy - All rights reserved

TECHNIC

AL SPECIFIC

ATIONS

Volume flow rate

Power (W)

SUPPLY/EXTRACT AIR VOLUMES

VALLOX 245 MV

50

100

150

200

250

300

350

50 %

40 %

30 %

60

80 100

120

160

140

dm³/s
(l/s)
m³/h

180 200 220

260 280

240

216 288 360 432 504

576 648 720 792 864 936 1008

300

1080

60 %

100 %

0

FAN INPUT POWER

60

80

100

120

160

140

180

200

220

260 280

240

216

288

360

432

504

576

648

720

792

864

936 1008

300

1080

50

100

150

200

250

300

350

50 %

30 %

40 %

400

100 %

60 %

m³/h

(l/s)

dm³/s

Volume flow rate 

(dm

3

/s)

Pressure loss in ducts. Total pressure (Pa)

Input power (total) (W)

Air flow (max) (dm3/s)

SFP =

SFP rate (Specific Fan Power)

recommended value <1.8 (kW m

3

/s)

extract air

supply air

Sound power level in the supply air duct (one duct)  

by octave band L

w

, dB

Sound power level in the extract air duct (one duct)  

by octave band L

w

, dB

Adjustment position

Adjustment position

Adjustment position (%)

30

40

50

60

100

30

40

50

60

100

Air flow dm³/s

132

160

190

213

250

143

170

204

230

278

Air flow m³/h

475

576

684

767

900

515

612

734

828

1001

Medium 

frequency 

of the 

octave 

band Hz

63

66

69

72

74

77

54

57

60

63

66

125

62

63

67

69

72

54

54

57

60

62

250

56

62

64

67

70

51

58

61

64

66

500

51

56

59

63

69

38

42

46

48

52

1000

51

55

58

61

64

37

41

45

48

51

2000

49

54

58

61

64

32

36

41

43

47

4000

36

42

48

52

57

25

28

30

34

38

8000

28

36

44

49

54

24

24

25

26

28

L

W

,dB 

L

WA

, dB(A)

68

71

74

76

79

58

62

64

67

70

56

60

64

67

71

46

50

53

57

59

Sound pressure level coming through the envelope of the unit in the room in which it is installed (10m² sound absorption)

Adjustment position / Air flows (supply/extract)

Adjustment position (%)

30

40

50

60

100

Air flow dm³/s

132/148

159/179

192/214

214/243

251/282

Air flow m³/h

475/533

572/644

691/770

770/875

904/1015

L

pA

, dB (A)

37

39

42

45

48

SOUND VALUES

TECHNICAL SPECIFICATIONS

Product title

Vallox 245 MV R

Vallox 245 MV L

Product number

3513100

3513200

Air volumes

 

Supply air

 

Extract air

245 dm

3

/s, 100 Pa

267 dm

3

/s, 100 Pa

Fans

 

Supply air

 

Extract air

0,170 kW 1,25 A EC

0,170 kW 1,25 A EC

Post-heating

Electrical resistor, 900 W

Electrical connection

230 V, 50 Hz,  14,5 A power plug

Pre-heating

Enclosure protection class

IP34

Additional heating

Electrical resistor, 1500 W

Heat recovery bypass

Automatic

Filters

 

Supply air

 

Extract air

ISO Coarse > 75 % + ISO ePM₁

ISO Coarse > 75 % 

Specific energy consumption (SEC)

 

in a cold climate 

 

in a temperate climate

A+

A

Operating efficiencies

 

 

Annual efficiency

 

Supply air efficiency

 

Specific Fan Power (SFP)

75 % A+

87,6 %

0,59 kW (150 dm

3

/s) A++

Dimensions

 (w x h x d)

1038 x 1241 x 773 mm

Weight

200 kg

TECHNIC

AL SPECIFIC

ATIONS

Содержание Vallox 245 MV VKL

Страница 1: ...Manual Model Vallox 245 MV Vallox 245 MV VKL Type A3732 A3732 Document D5337 Valid from 04 03 2020 Updated 05 02 2020 Ventilation unit MANUAL...

Страница 2: ...ing and closing the doors 9 Changing the filters 9 Cleaning the heat recovery cell 10 Condensing water 10 Cleaning the fans 11 Removing and cleaning the supply and extract air fans 11 Removing the res...

Страница 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Страница 4: ...Indicates a hazard that will result in death or serious injury if not avoided WARNING Indicates a hazard that can result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can...

Страница 5: ...smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation unit must be connected to the Internet via LAN and regis...

Страница 6: ...9 R model in the figure MAIN PARTS Vallox 245 MV Vallox 245 MV VKL Internal humidity sensor behind the electric box Internal carbon dioxide sensor behind the electric box Control panel Carbon dioxide...

Страница 7: ...ow for easier ventilation adjustment WARNING Water must at all times be kept out of the electrical system NOTE When installing the unit reserve a space of at least 800 mm in front of the unit for serv...

Страница 8: ...els Dimensions and duct outlets Dimensions Duct outlets R model Inner diameter of the female collar 250mm 1 Extract air from the apartment to the unit 2 Supply air from the unit to the apartment 3 Out...

Страница 9: ...ilters insects heavy pollen and other relatively large foreign objects out of the outdoor air Fine filter for supply air filters microscopic pollen and dust particles out of the supply air Coarse filt...

Страница 10: ...rs reassemble the ventilation unit in the reverse order 10 Close the doors Ensure that the safety switch catch of the door is touching the safety switch 11 Plug the ventilation unit back into the main...

Страница 11: ...eding it through the rubber feed Removing and cleaning the supply and extract air fans To clean the supply air fan 1 Disconnect the ventilation unit from the mains electricity supply 2 Open the doors...

Страница 12: ...connector of the resistor a Press down the locking device b Pull off the connector 5 Undo the two wing nuts connecting the resistor to the ventilation unit 6 Lift the resistor out of the ventilation...

Страница 13: ...2 46 48 52 1000 51 55 58 61 64 37 41 45 48 51 2000 49 54 58 61 64 32 36 41 43 47 4000 36 42 48 52 57 25 28 30 34 38 8000 28 36 44 49 54 24 24 25 26 28 LW dB LWA dB A 68 71 74 76 79 58 62 64 67 70 56 6...

Страница 14: ...9 61 66 500 59 66 46 52 1000 57 62 45 51 2000 57 62 41 47 4000 46 52 30 38 8000 40 47 25 28 LW dB LWA dB A 74 79 64 70 63 69 53 59 Sound pressure level coming through the envelope of the unit in the r...

Страница 15: ...erived from these measurements A Thermal input kW B Difference in water temperature C C Water flow dm s D Air flow dm s Vallox 245 MV liquid radiator ta1 15 C tf1 55 C Vallox 245 MV liquid radiator ta...

Страница 16: ...tor D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output T Supply air fan P Extract air fan M Damper motor TK Sa...

Страница 17: ...re Modbus B signal NTC External temperature sensor connector D I1 Digital input 1 D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay outpu...

Страница 18: ...ut EXTERNAL ELECTRICAL CONNECTION 3x1 5S 2x2x0 5 0 5 2x0 5 2x0 5 7028350 2014 08 29 JS 2x2x0 5 0 5 2x0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x2x0 5 0 5 2x0 5 2x0 5 CAT Analog input two different functions Potent...

Страница 19: ...2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output P Circulation pump V Solenoid valve EXTERNAL ELECTRICAL CONNECTION FOR CONTROLLING THE MLV DUCT RA...

Страница 20: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Страница 21: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Страница 22: ...er motor 930618 32 Liquid radiator actuator 946320 7 Post heating resistor 942220 20 Fine filter for supply air 978159 33 Liquid radiator control relay 948517 8 Additional heating resistor 942220 21 C...

Страница 23: ...CONFORMITY CERTIFICATES...

Страница 24: ...D5337 04 02 2020FIN 05 02 2020ENG PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270...

Отзывы: