CLEANING THE HEAT RECOVERY CELL

Check that the heat recovery cell (D) is clean roughly once a 

year when the filters are being replaced. Clean by washing as 

required.

IMPORTANT

If the unit has an enthalpy cell, it must not be washed. 

Only aluminium or plastic cells can be washed.

To check the heat recovery cell (HR cell):

1.  Disconnect the ventilation unit from the mains electricity 

supply.

2.  Lift the latch to open the door of the ventilation unit.

3.  Lift the door off.

CAUTION

The door is heavy.

4.  Pull the coarse filters (A, C) and filter supports out of the 

unit.

5.  Remove the sealing strip (E) above the HR cell.

6.  Remove the side sealing strip (F).

7.  Remove the fine filter (B).

8.  Lift and pull the cell (D) out of the unit.

IMPORTANT

Handle the cell carefully! For example, do not lift the 

cell by the layers. The cell layers are very thin and 

easily damaged.

9.  If the cell is dirty, clean it by immersing it in warm water, 

to which a small amount of a mild detergent has been 

added.

10.  Rinse the cell clean with a water spray. Do not use a high-

pressure cleaner.

11.  When all the water has drained from between the layers, 

reassemble the ventilation unit in the reverse order.

12.  Close the door. Ensure that the safety switch catch of the 

door is touching the safety switch.

13.  Plug the ventilation unit back into the mains.

14.  The heat recovery cell has now been checked and 

cleaned.

CONDENSING WATER

In the heating season, the extract air humidity condenses to 

water. In new buildings, condensation runoff can form rapidly. 

Condensed water must be able to freely leave the unit. 

At some time before the heating season begins (e.g. during 

autumn maintenance), check that the siphon or the condensing 

water outlet in the bottom pool are not clogged. To check this, 

pour some water into the pool. Clean as required.

NOTE

Some condensing water 

may have accumulated 

in the bottom pool 

of the unit; this is 

normal and requires no 

corrective action. 

WARNING

Water must at all times 

be kept out of the 

electrical system.

  

MAINTENANCE

S

C

A

B

Содержание TSK Multi Series

Страница 1: ...50 MV Vallox TSK Multi 50 MV EH Vallox TSK Multi 80 MV Vallox TSK Multi 80 MV EH Vallox TSK Multi 80 MV EHX Type A3609 1 A3609 B3608 1 B3608 B3608 2 Document D5321 Valid from 14 04 2020 Updated 18 03...

Страница 2: ...Before beginning maintenance work 9 Changing the filters 9 Cleaning the heat recovery cell 10 Condensing water 10 Cleaning the fans 11 Cleaning the supply air fan 11 Cleaning the extract air fan 12 T...

Страница 3: ...odifications or changes made to the software INTENDED USE All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to...

Страница 4: ...result in death or serious injury if not avoided IMPORTANT Indicates a hazard that can result in damage to property or loss of data if not avoided CAUTION Indicates a hazard that can result in minor o...

Страница 5: ...ws for controlling ventilation remotely also using e g a smartphone or tablet Also the unit software is updated automatically through the cloud service To connect to the cloud service the ventilation...

Страница 6: ...act air 7 Bypass damper of the HR cell 8 R model in the figure MAIN PARTS Vallox TSK Multi 50 MV and Vallox TSK Multi 80 MV Safety switch 9 Control panel 10 Internal humidity sensor 11 Internal carbon...

Страница 7: ...ront of the unit for servicing purposes The service space in front of Vallox TSK Multi 50 MV must be at least 530 mm The service space in front of Vallox TSK Multi 80 MV must be at least 600 mm NOTE T...

Страница 8: ...female 125 female E 87 110 F 197 254 G 86 110 H 161 200 I 161 200 J 86 96 K 96 96 L 206 231 M 498 624 N View from right O View from above P View from left Q Right side R Left side S Seen from behind L...

Страница 9: ...and dust particles out of the supply air Coarse filter for extract air filters the extract air and keeps the heat recovery cell clean To replace the filters 1 Disconnect the ventilation unit from the...

Страница 10: ...water to which a small amount of a mild detergent has been added 10 Rinse the cell clean with a water spray Do not use a high pressure cleaner 11 When all the water has drained from between the layer...

Страница 11: ...2 Unfasten the four screws to open the door of the unit 3 Lift the door off CAUTION The door is heavy 4 Remove the extract air filter C the cell top bracket E and the heat recovery cell D as described...

Страница 12: ...oving the supply air fan Figure 1 6 Remove the connector package from the wall 7 Separate the connectors from each other 8 Tilt the fan to the left and turn 90 9 Tilt the fan forward to pull it out of...

Страница 13: ...ressure loss in the extract and supply air ducts extract air supply air TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS AIR FLOWS AND SOUND VALUES Pressure loss in ducts Total pressure Pa Volume flo...

Страница 14: ...3 66 68 72 72 41 45 50 54 56 58 60 62 64 Sound pressure level coming through the envelope of the unit in the room in which it is installed 10m sound absorption Adjustment position Air flows supply ext...

Страница 15: ...vel in the supply air duct one duct by octave band Lw dB Adjustment position Sound power level in the extract air duct one duct by octave band Lw dB Adjustment position Adjustment position 10 20 30 40...

Страница 16: ...TSK Multi 50 MV EH Vallox TSK Multi 80 MV EH EHX R2 Additional heating resistor with 90 C and 130 C overheating protection Vallox TSK Multi 80 MV EHX BK Black BU Blue BN Brown WT White GY Grey YE Yell...

Страница 17: ...D I2 Digital input 2 11V1 11 1 V operating voltage AN I Analog input 0 10VDC RM I 24V relay input RM O 24V relay output EXTERNAL ELECTRICAL CONNECTION Analog input two different functions Potential fr...

Страница 18: ...the supply air temperature will be maintained at the level specified in the temperature setting In winter the duct radiator will turn on when the outdoor temperature falls below the winter setting Ma...

Страница 19: ...ve Not included in the delivery The valve that is chosen must be compatible with the heat collection circuit fluid for example ELV05006 Stig Wahlstr m K Condensing water tube Not included in the deliv...

Страница 20: ...External Modbus A signal MB_B External Modbus B signal 24V 24V voltage DC GND Digital and analog ground potential RS_A Local hardware Modbus A signal RS_B Local hardware Modbus B signal NTC External t...

Страница 21: ...tional heating resistor L model Vallox TSK Multi 80 MV 942211 15 Side sealing strip of the heat recovery cell Vallox TSK Multi 50 MV 3356300 15 Side sealing strip of the heat recovery cell Vallox TSK...

Страница 22: ...CONFORMITY CERTIFICATES...

Страница 23: ......

Страница 24: ...www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Aftersales 358 10 7732 270 D5321 18 03 2020FIN 18 03 2020ENG PDF...

Отзывы: