MEASURING AND ADJUSTING THE AIR FLOWS

Standard ventilation 

The volume flow rate of the air inside the cooker hood is 

measured with the damper closed and, where required, 

adjusted based on the static pressure loss and the 

performance scheme of the cooker hood. 

•  Measure the static pressure loss of the cooker hood by 

pushing the probe through the hole in the damper (see 

the figure). 

•  Determine the volume flow rate from the performance 

scheme based on the measured pressure and the 

number of open holes in the damper. 

Adjustment:

•  Cover the required number of holes in the damper with 

the magnetic strip that is delivered with the cooker 

hood.

MANU

AL

dp

>2 x ø

ø

Boost ventilation

The volume flow rate of the air inside the cooker hood 

is measured with the damper open based on the 

static pressure loss and the performance scheme of 

the cooker hood. 

•  Measure the static pressure loss of the cooker hood. 

The measuring point must be located 2 times the 

duct diameter above the outlet collar of the cooker 

hood (see figure).

•  Determine the volume air flow based on the 

measured pressure and the performance scheme 

(with the damper open).

dp

K VALUES

Adjustment 

position

Holes of 

the damper 

open

K value

2

2

0.5

3

3

0.6

4

4

0.8

5

5

1.0

6

6

1.1

7

7

1.3

8

8

1.4

Damper 

open

4.9

  S

TAND

ARD VENTILA

TION

5

6

7

8

15

20

30

40

50

60 70

10

20

30

40

50

60

70

80

90

200

250

300

400

500

10

100

Measured pressure with a probe P

a without a grease filter

Air flow dm³/s

4

3

2

5 6 7 8

Measured pressure with standard ventilation

Damper open

Adjustment position

L

pA,

bB(A)

Содержание Delico PTD AC

Страница 1: ...Type A279844 1 The Vallox Delico PTD AC control hood is suited to controlling AC roof fans and AC ventilation units The cooker hood is designed to be used above the cooker top as a general extraction...

Страница 2: ...the light switch The light is dimmable Adjust the brightness by pressing the light switch until the brightness is adequate Ventilation modes Select the ventilation mode by pressing the ventilation mo...

Страница 3: ...kind of alarm is noticed before fire damage it can be acknowledged by pressing any of the cooker hood buttons Pre selection of light brightness To modify the pre selection of light brightness 1 Turn o...

Страница 4: ...combustion gases e g from a wood or gas burning fireplace cooker or stove CAUTION Regulations on leading extraction air outdoors must be observed 293 310 311 333 20 45 6 8 9 10 Where needed install a...

Страница 5: ...OOD S1 S2 S3 out N N L E g Vallox 95 75 Distribution board L N 90V 110V 120V 160V and 180V free L 230V L 230V 135V 70V TRANSFORMER Underneath the lid of the left electric box L N L Connection box BN B...

Страница 6: ...0 V At home 135 V Boost 230 V To change these values move the transformer wires to more suitable connectors see the wiring diagrams SETTING VENTILATION MODES EXTERNAL ELECTRICAL CONNECTION TO A ROOF F...

Страница 7: ...NUAL dp 2 x Boost ventilation The volume flow rate of the air inside the cooker hood is measured with the damper open based on the static pressure loss and the performance scheme of the cooker hood Me...

Страница 8: ...Vallox DelicoPTD AC D10029 18 12 2020 www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer service 358 10 7732 200 Technical support 358 10 7732 270...

Отзывы: