background image

MANU

AL

D

39

25

/9.

5.

20

17

 

External electrical connection

Standard ventilation

The volume flow rate of the air inside the cooker hood is 

measured with the damper closed.
Measuring

•  The air flow measuring tubes are located behind the cooker 

hood light on the right side.

•  Connect the differential pressure gauge to the measuring 

tube that is marked with a “min.” sticker. The enclosed 

figure illustrates the measuring principle.

Adjustment

•  Cover the required number of holes in the damper with the 

magnetic strip that is delivered with the cooker hood.

•  Determine the volume flow rate from the performance 

scheme based on the measured pressure and the number 

of open holes in the damper.

Boost ventilation

The volume flow rate is measured and adjusted with the damper 

open.
Measuring

•  The measuring tubes should be connected as specified in 

the standard ventilation section.

•  The differential pressure gauge is connected to both 

measuring tubes. The enclosed figure illustrates the 

measuring principle.

•  Determine the volume air flow from the performance 

scheme based on the measured pressure.

Adjustment

•  Cover the required number of holes in the damper with the 

magnetic strip that is delivered with the cooker hood.

ALARM

TACHO

GND

PWM

OPT
+  -

DAMP
IN OUT

MODE
IN OUT

F ALARM

  RS 485
A  B GND

N

L

DAMPER

1    2    3

LIGHT

N    L

FAN

N    L

IN OUT

PE

EXTRA

POSITION

OF THE FLAP

CONTACT DATA

CONTACT DATA

GUARD FUNCTION

STANDARD VENTILATION  

(SETTINGS 3---8)
- damper closed
- available settings
- 2  =  20 holes open/damper
- 3  =  30 holes open/damper
- 4  =  40 holes open/damper
- 5  =  50 holes open/damper
- 6  =  60 holes open/damper
- 7  =  70 holes open/damper
- 8  =  80 holes open/damper

BOOST VENTILATION  

(SETTINGS 16---24)
- damper open
- available settings
- 16  =  164 holes open  

 

  (2 magnetic strips)

- 20 =  203 holes open  

 

  (1 magnetic strip)

- 24 =  242 holes open  

 

  (all are open)

A

A

 

A

A

 

Measuring and adjusting performance values

Measuring  

standard ventilation

Measuring  

boost ventilation

5

6

7

8 9

20

30

40

50

60

10

20

30

40

50

60

70

80

90

200

300

400

100

45

40

35

30

25

45

40

35

30

25

24

20

16

LpA, dB(A)

4 5

3

8

7

2

6

Air flow, dm³/s

Static pressure loss Pa

Adjustment position 

Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND 

www.vallox.com | Ex358 10 7732 200 | Afte358 10 7732 270

Отзывы: