background image

VALLOX 90K SC

© VALLOX • We reserve the right to make changes without prior notification.

1.09.347E

/30.8.2006/PDF/Premedia Focus

Vallox Oy   FIN-32200 Loimaa   T358 2 7636 300   T358 2 7631 539

Internet: www.vallox.com

REASON

•  Air cools down in the attic ducts.
•  The heat recovery cell is frozen, which is why extract air cannot heat outdoor air.
•  The preheating radiator does not work.
•  The extract air filter or the cell is clogged.
•  The initial adjustment of ventilation has not been done.

DO THIS

• Measure the temperature of supply air in the unit and compare it with the air coming

from the valve.

• Check the insulation of the attic ducts.
• Check the operation of the defrost thermostat and preheating resistor (see section 2.6

“Defrosting” on page 5). You can turn the defrost thermostat clockwise. In this case
there will probably be no freezing, but extract air can be too warm when going out.
The defrost thermostat can also be turned anticlockwise. In this case, the risk of
freezing of the heat recovery cell will increase. According to the factory setting, the
defrost thermostat works at +5 

°

C.

• Check that the filters and the heat recovery cell are clean.
• Check the initial adjustment.

1. Outdoor air coming to the dwelling is cold.

REASON

• The heat recovery cell defrost function works and prevents the cell from freezing.

DO THIS

• If you want the fan to stop at temperatures lower than the preset value, you can decrease

the threshold value of the thermostat by 1 to 2 

°

C.

NOTE. If you decrease the threshold value too much, the cell may freeze. See item1.

2. Supply air fan keeps stopping

4. TROUBLESHOOTING

Содержание 90k SC

Страница 1: ...nges without prior notification 1 09 347E 30 08 06 Code 3522 VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE SUPPLY AND EXTRACT AIR VENTILATION WITH HEAT RECOVERY SC Code 3522 VALLOX 90K SC R 3295200 VALL...

Страница 2: ...adjustment p 4 2 2 Selection of fan speed p 4 2 3 Heat recovery bypass p 5 2 4 Air filtering p 5 2 5 Defrosting p 5 2 6 Stopping the supply air fan p 5 2 7 Outdoor air preheating p 5 2 8 Post heating...

Страница 3: ...t of the indoor air stay at a healthy level Recommended humidity content of good indoor air is approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in...

Страница 4: ...ly pressured air in the dwelling penetrates the outer envelope of the building and between windows which may cause humidity damage during the heating season In normal conditions basic ventilation with...

Страница 5: ...s risen by circa three degrees i e to 8 C The limit of the thermostat F can be adjusted at the back of the heat recovery cell If the unit includes a preheating radiator G the supply air fan cannot be...

Страница 6: ...oothly Do not handle the filters with force When washing is done properly filters stand cleaning 3 to 4 times In other words you have to replace them at least every two years The fine filter E is not...

Страница 7: ...flow out from the ventilation unit without hindrance In connection with maintenance e g in autumn before the beginning of the heating season make sure that the condensing water outlet L in the bottom...

Страница 8: ...ing resistor see section 2 6 Defrosting on page 5 You can turn the defrost thermostat clockwise In this case there will probably be no freezing but extract air can be too warm when going out The defro...

Отзывы: